| 2018-03-23 11:44:22 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 2) SHOW THE LOCATION OF ALL OPERABLE DOORS AND WINDOWS |
| | IN RELATION TO THE LOCATION OF THE TANKLESS WATER |
| | HEATER. THE TANKLESS WATER HEATER SHALL BE A MINIMUM OF |
| | 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | DESCRIPTION OF WORK ON THE APPLICATION NOTES THAT THE |
| | TANKLESS WATER HEATER IS BEING MOVED. THE SUBMITTED |
| | PLAN IS UNCLEAR AS TO THE EXISTING LOCATION AND THE NEW |
| | LOCATION. CLARIFY. |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. 2017 FBC-FUEL GAS SEC. G2407.1, G2439.4, |
| | G2406.2, G2407.5. |
| | 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2. THIS APPLIES TO THE LOW |
| | PRESSURE GAS PIPING FROM 2 PSI TO 1/2 LB REGULATOR FOR |
| | THE DRYER, STOVE AND FIREPLACE. |
| | 7) THE PLAN NOTES "S.S GAS PIPING IN SLEEVE UNDER |
| | FLOOR". I ASSUME THIS IS CSST MATERIAL. SUBMIT THE |
| | CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS |
| | STEEL TUBING AND TWO COPIES OF THE APPLICABLE SIZING |
| | TABLE FOR THIS PORTION OF THE SYSTEM.2017 FBC- |
| | RESIDENTIAL SEC.G2413.3. SHOW THE TYPE OF SLEEVE |
| | MATERIAL AND SIZE. |
| | 8) INDICATE THE TYPE OF PIPING ON THE EXISTING |
| | SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 9) IS THE FLOOR A WOOD FLOOR AND THE PIPING BEING |
| | INSTALLED IN A CRAWL SPACE? IS IT BEING INSTALLED |
| | UNDERGROUND? THE SLEEVE SHALL BE VENTED IN ACCORDANCE |
| | WITH 2017 FBC-RES. SEC.2415.14. CLARIFY AND PROVIDE |
| | ADDITTIONAL INFORMATION.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE |
| | LOCATION OF THE GAS APPLIANCES. THE FLOOR PLAN CAN BE |
| | HAND DRAWN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) SIZE ALL SECTIONS OF PIPING DOWNSTREAM OF THE |
| | REGULATOR AT THE TANKLESS WATER HEATER INCLUDING ALL |
| | SECTIONS BETWEEN THE TEES FOR EACH BRANCH TO DRYER, |
| | STOVE AND FIREPLACE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |