Plan Review Notes
Plan Review Notes For Permit 18030801
Permit Number 18030801
Review Stop G
Sequence Number 1
Notes
Date Text
2018-03-23 11:44:221) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 2) SHOW THE LOCATION OF ALL OPERABLE DOORS AND WINDOWS
 IN RELATION TO THE LOCATION OF THE TANKLESS WATER
 HEATER. THE TANKLESS WATER HEATER SHALL BE A MINIMUM OF
 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 DESCRIPTION OF WORK ON THE APPLICATION NOTES THAT THE
 TANKLESS WATER HEATER IS BEING MOVED. THE SUBMITTED
 PLAN IS UNCLEAR AS TO THE EXISTING LOCATION AND THE NEW
 LOCATION. CLARIFY.
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. G2407.1, G2439.4,
 G2406.2, G2407.5.
 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2. THIS APPLIES TO THE LOW
 PRESSURE GAS PIPING FROM 2 PSI TO 1/2 LB REGULATOR FOR
 THE DRYER, STOVE AND FIREPLACE.
 7) THE PLAN NOTES "S.S GAS PIPING IN SLEEVE UNDER
 FLOOR". I ASSUME THIS IS CSST MATERIAL. SUBMIT THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING AND TWO COPIES OF THE APPLICABLE SIZING
 TABLE FOR THIS PORTION OF THE SYSTEM.2017 FBC-
 RESIDENTIAL SEC.G2413.3. SHOW THE TYPE OF SLEEVE
 MATERIAL AND SIZE.
 8) INDICATE THE TYPE OF PIPING ON THE EXISTING
 SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 9) IS THE FLOOR A WOOD FLOOR AND THE PIPING BEING
 INSTALLED IN A CRAWL SPACE? IS IT BEING INSTALLED
 UNDERGROUND? THE SLEEVE SHALL BE VENTED IN ACCORDANCE
 WITH 2017 FBC-RES. SEC.2415.14. CLARIFY AND PROVIDE
 ADDITTIONAL INFORMATION.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF THE GAS APPLIANCES. THE FLOOR PLAN CAN BE
 HAND DRAWN.WPB AMEND. TO FBC SEC. 107.2.1.
 11) SIZE ALL SECTIONS OF PIPING DOWNSTREAM OF THE
 REGULATOR AT THE TANKLESS WATER HEATER INCLUDING ALL
 SECTIONS BETWEEN THE TEES FOR EACH BRANCH TO DRYER,
 STOVE AND FIREPLACE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  