| Plan Review Notes For Permit 18030798 |
| Permit Number |
18030798 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-23 18:57:33 | RE-ROOF REVISION , BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ACCORDING TO THE WITHDRAWAL RESISTANCE TEST (TAS | | | 105) SUBMITTED THE CHOSEN FASTENERS ARE INSUFFICIENT. | | | NEED TO FOLLOW ENGINEER RECOMMENDATIONS. SEC. 1609.1 | | | FBC. | | | | | | 2- THE DESIGN PRESSURES FOR SELECTED SYSTEM LWC-33 IS | | | -52.5 PSF. (SEE PREVIOUS REVISION 17061315) NEED TO | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | PERIMETER AND CORNER AREAS AS REQUIRED BY NOTE #8 OF | | | FLORIDA PRODUCT APPROVAL SUBMITTED. NOTE: ENGINEER | | | DOING THE CALCULATIONS TO COORDINATE WITH THE TAS 105 | | | RESULTS. SEE ITEM #1 ABOVE. | | | SEC. 1609.1 FBC. | | | | | | NOTE: | | | CONTRACTOR TO PAY THE $75 PERMIT EXTENSION FEE AS | | | DISCUSSED BY MRS. YAILEN WITH SAMANTHA HILL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|