| 2018-08-22 16:39:07 | 08/22/2018 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SECOND REQUEST, PLUMBING RISER DIAGRAM REQUIRED |
| | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) |
| | RESIDENTIAL PLUMBING |
| | 2. HOT WATER HEATER DISCHARGE ON P-1 DETAIL CALL FOR |
| | THE DRAIN TO DISCHARGE IN THE GARAGE BUT THE HEATER IS |
| | NOT IN THE GARAGE. IT MAY DISCHARGE OUTSIDE THROUGH A |
| | DRAIN LINE PLEASE CORRECT, FBC R 2804.6.1. THE PAN |
| | DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER A |
| | SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR SHALL |
| | EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE |
| | NOT LESS THAN 6 INCHES FBC R 2801.6.2 |
| | 4. SECOND REQUEST, WASHING MACHINE BOX SHALL BE ABLE TO |
| | BE SHUT OFF WITHOUT MOVING UNIT, PLEASE PROVIDE VALVES |
| | A LOCATION THAT CAN BE REACHED FBC R 2903.9.3 FIXTURE |
| | VALVES AND ACCESS. FIXTURE VALVES AND ACCESS. |
| | ACCESSIBLE, SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL |
| | OF AN ACCESS PANEL OR SIMILAR REMOVABLE OBSTRUCTION. |
| | 5. THE SECOND REQUEST, ON P-1, HAS A NOTE THAT REFERS |
| | TO MIAMI-DADE CODE SECTION 8-31 MAXIMUM FLOW RATE WHICH |
| | IS NOT A ENFORCE SECTION BY THIS MUNICIPALITY, PLEASE |
| | DELETE AMENDED CONSTRUCTION DOCUMENTS FBC WPB A 107.4 |
| | 6. THE SECOND REQUEST, WATER HEATER E.F AT 0.91 NEW |
| | CODE REQUIRES .095 AS PER NECA APRIL 15, 2015 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |