2018-04-04 15:38:30NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- REVISE MECHANICAL FLOOR PLAN. THE RETURN AIR CAN NOT
 BE LESS THAN 10 FEET FROM THE KITCHEN RANGE. REVISE AS
 REQUIRED. SEC. M1602.2 FBC-RESIDENTIAL.
  
 2- THE TRANSFER DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN AIR
 SEC. M1602.3. NEED TO INCLUDE ALL THE SUPPLY AIR
 ENTERING THE MASTER SUITE.
  
 M1602.3 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 (1).TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (2).TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-WALL TRANSFER GRILLES AND USING AN UNRESTRICTED
 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (3).HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
  
  
 3- IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE
 DONE BASED ON THE INFORMATION USED IN THE ENERGY
 CALCULATIONS DONE BY THE SAME ENGINEER. ENERGY
 CALCULATIONS NEED TO BE REVISED. SEE COMMENTS IN THE
 BUILDING REVIEW REGARDING THE ENERGY CALCULATIONS.
 REVISE THE EQUIPMENT SIZING CALCULATIONS REFLECTING THE
 CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ADDRESS SPECIFIED IN THE EQUIPMENT SIZING
 CALCULATIONS IS INCORRECT. REVISE AS REQUIRED TO MATCH
 ACTUAL LOCATION OF HOUSE. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ENGINEER SIGNING AND SEALING THE CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER 471 F.S.
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 4- ENGINEER TO REVISE THE DUCT HANGING DETAILS TO MATCH
 ACTUAL CONSTRUCTION SHOWN ON PLANS. THIS IS NOT WOOD
 FRAMED CEILING. SEC. R301.1 FBC-RESIDENTIAL.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  