Plan Review Notes
Plan Review Notes For Permit 18030768
Permit Number 18030768
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-23 14:15:55****CORRECTIONS****
 W.P.B. PERMIT: 18030768
 REVIEWED: AUGUST 23, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- OK
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
 3-2-[FBC R807]THIS IS FIRE DEPARTMENT ACCESS AND IS
 REQUIRED.
  
 4- PLANS NEED TO SPECIFY THE ATTIC LIVE LOADS AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: KEEP IN
 CONSIDERATION FOOTNOTE "G".
 4-2-ATTIC WILL BE ACCESSIBLE AND WILL NEED TO BE ABLE
 TO CARRY LIVE LOAD. PLEASE UPDATE WALL TYPES ON A-3 TO
 SHOW THAT THEY WILL BEAR THE FRAMED CEILING AND LIVE
 LOAD. ALSO, THE CEILNG FRAMING MEMBERS WILL NEED TO
 SUPPORT LIVE LOAD SPECIFIED. PLEASE SHOW WHAT GAUGE
 STEEL STUD TO SUPPORT LIVE LOAD.
  
  
 5- OK
  
 6- OK
  
 7- OK
  
 8- OK
  
 9- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 SEC. R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 9-2-DRAINAGE PLAN TO SHOW ELEVATIONS THAT KEEP DRAINAGE
 ON PROPERTY. ALSO, PLEASE PROVIDE 2 COPIES OF SURVEY.
 YOU CAN USE THE SURVEY AS BASIS FOR DRAINAGE PLAN.
  
 10- OK
  
 11- FLAT ROOF AREA ABOVE BEDROOM #1: SPECIFY SIZE OF
 CONCRETE SCUPPER AND PROVIDE COMPLETE INFORMATION
 (LOCATION AND SIZE) OF OVERFLOW DRAIN/SCUPPERS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
 11-2-I SEE A SCUPPER IN PLAN VIEW, BUT NO NOTES ABOUT
 IT. PLEASE PROVIDE DRAINAGE CALCULATIONS FOR FLAT ROOF
 AND INCLUDE THE WATER BEING CONTRIBUTED BY 6:12 ROOF
 AROUND IT. REFER TO [FBC R903.4]FOR SCUPPERS AND
 OVERFLOW DRAINS.
  
 12- OK
  
 13- PROVIDE DETAILS AND SPECIFICATIONS FOR DOORS AND
 WINDOWS STRUCTURAL BUCK DETAILS. SEC. R301.1
 FBC-RESIDENTIAL.
 13-2-NOT PROVIDED. THESE ARE TYPICAL OPENING DETAILS
 THAT WOULD SHOW BUCK ATTACHMENT TO OPENINGS.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE 42" HIGH WALL SHOWN ON PLANS. SEC.
 R301.1 FBC-RESIDENTIAL.
 14-2-THIS IS THE WALL ON PATIO. PROVIDE DETAIL AS
 PREVIOUSLY REQUESTED.
  
 15- PROVIDE DETAILS AND SPECIFICATIONS FOR THE ROOF
 BATTENS THAT ARE GOING TO SUPPORT THE PROPOSED METAL
 ROOFING SYSTEM. COORDINATE WITH METAL ROOFING PRODUCT
 APPROVAL. SEC. R301.1 FBC-RESIDENTIAL.
 15-2-PROVIDE ROOFING SUBMITTAL, OR INDICATE THAT IT
 WILL BE DEFERRED UNTIL ROOFING SUB PERMIT.
  
 16- OK
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS.
  
 F) SLIDING WINDOWS AS SHOWN ON PLANS.
  
 G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 H) FRENCH DOORS AS SHOWN ON PLANS.
  
 I) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE.
  
 L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL. COORDINATE WITH ITEM #15
 ABOVE.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 18-2-PROVIDE PRODUCT APPROVALS, OR INDICATE THAT THEY
 WILL BE DEFERRED.
  
 [FBC AMENDED 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS
 SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
 19- OK
  
 20- IMPORTANT: CONTRACTOR TO COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) FOR INSPECTIONS OF SPECIAL
 CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY
 AMENDMENTS TO AVOID CONFLICTS/DELAYS.
 KEN CONRAD (561)805-6666 OR E-MAIL [email protected]
  
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  