Plan Review Notes
Plan Review Notes For Permit 18030768
Permit Number 18030768
Review Stop B
Sequence Number 1
Notes
Date Text
2018-04-04 17:02:38NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- ENTRY DOOR DOESN'T COMPLY WITH EGRESS. REVISE AS
 REQUIRED. SEC. R311.2 FBC-RESIDENTIAL.
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 4- PLANS NEED TO SPECIFY THE ATTIC LIVE LOADS AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: KEEP IN
 CONSIDERATION FOOTNOTE "G".
  
 5- PROVIDE COMPLETE FRAMING PLAN, DETAILS AND
 SPECIFICATIONS FOR ATTIC FLOOR. SEC R301.1
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM #4 ABOVE
 AND MECHANICAL PLAN.
  
 6- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR
 INTERIOR PARTITIONS FRAMING. SPECIFY ALL FRAMING
 MEMBERS AND SPACING. PROVIDE COMPLETE
 DETAIL/SPECIFICATIONS FOR FRAMING AROUND DOOR OPENING.
 PROVIDE SPECIFICATIONS FOR WALLS IN WET AREAS. , ETC.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- CONCRETE STRENGTH SPECIFIED ON SHEET S-1 AND S-2 IS
 NOT CLEAR. CONCRETE STRENGTH SPECIFIED AT THE BOTTOM
 LEFT BY THE STRUCTURAL DESIGN LOADS IS 4,000 PSI WHILE
 CONCRETE STRENGTH SPECIFIED AT THE BOTTOM RIGHT BY THE
 ENGINEER'S STATEMENT IS 3,000PSI. REVISE AS REQUIRED TO
 MATCH AND COORDINATE WITH STRUCTURAL CALCULATIONS
 SUBMITTED ALSO. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- STRUCTURAL CALCULATIONS NEED TO BE REVISED. THE
 CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT THE FBC
 5TH EDITION (2014). CHAPTER 553 FLORIDA STATUTE. UPDATE
 AS REQUIRED.
  
 9- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 SEC. R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 10- NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320 FBC-RESIDENTIAL.
  
 11- FLAT ROOF AREA ABOVE BEDROOM #1: SPECIFY SIZE OF
 CONCRETE SCUPPER AND PROVIDE COMPLETE INFORMATION
 (LOCATION AND SIZE) OF OVERFLOW DRAIN/SCUPPERS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
  
 12- PROVIDE EVALUATION REPORT FOR THE WALL AND CEILING
 INSULATION SHOWING THE R-VALUES SPECIFIED ON PLANS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R316
 FBC-RESIDENTIAL.
  
 13- PROVIDE DETAILS AND SPECIFICATIONS FOR DOORS AND
 WINDOWS STRUCTURAL BUCK DETAILS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE 42" HIGH WALL SHOWN ON PLANS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 15- PROVIDE DETAILS AND SPECIFICATIONS FOR THE ROOF
 BATTENS THAT ARE GOING TO SUPPORT THE PROPOSED METAL
 ROOFING SYSTEM. COORDINATE WITH METAL ROOFING PRODUCT
 APPROVAL. SEC. R301.1 FBC-RESIDENTIAL.
  
 16- ENERGY CALCULATIONS FORM R405-2017 SUBMITTED:
 A) THE CARDINAL ORIENTATION OF THE ENERGY CALCULATIONS
 SUBMITTED DON'T MATCH ACTUAL ORIENTATION OF THE
 PROPOSED BUILDING. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: IF SAME HOUSE WILL BE BUILT ON DIFFERENT
 LOCATIONS, THEN WORST CASE SCENARIO MAY BE COMPLETED.
 SEE SEC. R405.4.2 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE ADDRESS IS INCORRECT. NEED THE OWNER'S AND
 BUILDER'S INFORMATION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) WALL INFORMATION ON ITEM #9 DOESN'T MATCH PLANS.
 REVISE TYPE OF CONSTRUCTION AND INSULATION R VALUE TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) CEILING INFORMATION ON ITEM #10 DOESN'T MATCH PLANS.
 REVISE INSULATION R VALUE TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) ENGINEER SIGNING AND SEALING THE CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER 471 F.S.
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 F) CLARIFY WHY THE R-VALUE SHOWN ON PAGE 2 OF 4 DOESN'T
 MATCH THE R-VALUE SHOWN ON ITEM #10 ON PAGE 1 OF 4.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-RESIDENTIAL.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS.
  
 F) SLIDING WINDOWS AS SHOWN ON PLANS.
  
 G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 H) FRENCH DOORS AS SHOWN ON PLANS.
  
 I) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE.
  
 L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $166,424 AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS
 $3402.65.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 20- IMPORTANT: CONTRACTOR TO COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) FOR INSPECTIONS OF SPECIAL
 CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY
 AMENDMENTS TO AVOID CONFLICTS/DELAYS.
 KEN CONRAD (561)805-6666 OR E-MAIL [email protected]
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  