| Date |
Text |
| 2018-10-24 11:06:52 | |
| | THE STRUCTURAL SHELL OF THIS BUILDING WILL REQUIRE A |
| | RESIDENT INSPECTOR AS IT REQUIRES SPECIAL SHORING PLAN |
| | FOR THE STRUCTURAL SYTEM BEING USED. |
| | PLEASE CONTACT ME FOR THE FORM TO BE FILLED OUT AND |
| | ADDITIONAL REQUIREMENTS OF USING A RESIDENT INSPECTOR. |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | NO COMMENT RESPONSE SHEET WAS PROVIDED. |
| | PLEASE VERIFY THAT THE PRODUCT APPROVALS LISTED BELOW |
| | WILL BE DEFERRED SUBMITTALS. |
| | |
| | PROVISOS: |
| | |
| | PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| | |
| | B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON |
| | PLANS. |
| | |
| | C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| | |
| | D) CASEMENT WINDOWS AS SHOWN ON PLANS. |
| | |
| | E) FIXED WINDOWS AS SHOWN ON PLANS. |
| | |
| | F) SLIDING WINDOWS AS SHOWN ON PLANS. |
| | |
| | G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED |
| | DESIGN PRESSURES. |
| | |
| | H) FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | I) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| | |
| | J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T |
| | HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE. |
| | |
| | L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH |
| | SEC. R905.15 FBC-RESIDENTIAL. COORDINATE WITH ITEM #15 |
| | ABOVE. |
| | |
| | DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |