| Date |
Text |
| 2018-07-31 18:44:13 | 07/31/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SECOND REQUEST, PLUMBING RISER DIAGRAM REQUIRED WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL |
| | PLUMBING |
| | 2. SECOND REQUEST, WASHING MACHINE BOX SHALL BE ABLE TO |
| | BE SHUT OFF WITHOUT MOVING UNIT, PLEASE PROVIDE VALVES |
| | A LOCATION THAT CAN BE REACH FBC R 2903.9.3 FIXTURE |
| | VALVES AND ACCESS. |
| | 3. SECOND REQUEST, ON P-1 HAS A NOTE THAT REFERS TO |
| | MIAMI-DADE CODE SECTION 8-31 MAXIMUM FLOW RATE WHICH IS |
| | NOT A ENFORCE SECTION BY THIS MUNICIPALITY, PLEASE |
| | DELETE AMENDED CONSTRUCTION DOCUMENTS FBC WPB A 107.4 |
| | 4. WATER HEATER EF 0.91 ON A 50 GALLON ON FORM |
| | R405-2017 IS NOT ACCORDANCE WITH 2017 FBC RE 403.6.2 |
| | AND STATE RESIDENTIAL UNITS SHALL MEET THE MINIMUM |
| | EFFICIENCIES OF TABLE C404.2, IN CHAPTER 4 OF FBC |
| | ENERGY CONSERVATION. IT IS CALLING FOR A 0.97 ON |
| | ELECTRIC BUT TELL ME HOW YOU CAME UP WITH 0.91 OR YOU |
| | CAN REFER TO NEACA HOT WATER REGULATION 2015, PLEASE |
| | VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU |
| | LATIONS/ FOR FURTHER DETAILS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |