| 2018-08-23 14:18:56 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18030765 |
| | REVIEWED: AUGUST 23, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, |
| | ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO |
| | PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS |
| | WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID |
| | RECEIPT MUST BE RETURNED TO THE CITY BUILDING |
| | DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED. |
| | FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT |
| | (561) 233-5025. |
| | |
| | 2- OK |
| | |
| | 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED |
| | BY SEC. R807 FBC-RESIDENTIAL. |
| | 3-2-[FBC R807]THIS IS FIRE DEPARTMENT ACCESS AND IS |
| | REQUIRED. |
| | |
| | 4- PLANS NEED TO SPECIFY THE ATTIC LIVE LOADS AS |
| | REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: KEEP IN |
| | CONSIDERATION FOOTNOTE "G". |
| | 4-2-ATTIC WILL BE ACCESSIBLE AND WILL NEED TO BE ABLE |
| | TO CARRY LIVE LOAD. PLEASE UPDATE WALL TYPES ON A-3 TO |
| | SHOW THAT THEY WILL BEAR THE FRAMED CEILING AND LIVE |
| | LOAD. ALSO, THE CEILNG FRAMING MEMBERS WILL NEED TO |
| | SUPPORT LIVE LOAD SPECIFIED. PLEASE SHOW WHAT GAUGE |
| | STEEL STUD TO SUPPORT LIVE LOAD. |
| | |
| | |
| | 5- OK |
| | |
| | 6- OK |
| | |
| | 7- OK |
| | |
| | 8- OK |
| | |
| | 9- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE |
| | DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS |
| | SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM). |
| | 9-2-DRAINAGE PLAN TO SHOW ELEVATIONS THAT KEEP DRAINAGE |
| | ON PROPERTY. ALSO, PLEASE PROVIDE 2 COPIES OF SURVEY. |
| | YOU CAN USE THE SURVEY AS BASIS FOR DRAINAGE PLAN. |
| | |
| | 10- OK |
| | |
| | 11- FLAT ROOF AREA ABOVE BEDROOM #1: SPECIFY SIZE OF |
| | CONCRETE SCUPPER AND PROVIDE COMPLETE INFORMATION |
| | (LOCATION AND SIZE) OF OVERFLOW DRAIN/SCUPPERS AS |
| | REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL. |
| | 11-2-I SEE A SCUPPER IN PLAN VIEW, BUT NO NOTES ABOUT |
| | IT. PLEASE PROVIDE DRAINAGE CALCULATIONS FOR FLAT ROOF |
| | AND INCLUDE THE WATER BEING CONTRIBUTED BY 6:12 ROOF |
| | AROUND IT. REFER TO [FBC R903.4]FOR SCUPPERS AND |
| | OVERFLOW DRAINS. |
| | |
| | 12- OK |
| | |
| | 13- PROVIDE DETAILS AND SPECIFICATIONS FOR DOORS AND |
| | WINDOWS STRUCTURAL BUCK DETAILS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | 13-2-NOT PROVIDED. THESE ARE TYPICAL OPENING DETAILS |
| | THAT WOULD SHOW BUCK ATTACHMENT TO OPENINGS. |
| | |
| | 14- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE 42" HIGH WALL SHOWN ON PLANS. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | 14-2-THIS IS THE WALL ON PATIO. PROVIDE DETAIL AS |
| | PREVIOUSLY REQUESTED. |
| | |
| | 15- PROVIDE DETAILS AND SPECIFICATIONS FOR THE ROOF |
| | BATTENS THAT ARE GOING TO SUPPORT THE PROPOSED METAL |
| | ROOFING SYSTEM. COORDINATE WITH METAL ROOFING PRODUCT |
| | APPROVAL. SEC. R301.1 FBC-RESIDENTIAL. |
| | 15-2-PROVIDE ROOFING SUBMITTAL, OR INDICATE THAT IT |
| | WILL BE DEFERRED UNTIL ROOFING SUB PERMIT. |
| | |
| | 16- OK |
| | |
| | 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| | |
| | B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON |
| | PLANS. |
| | |
| | C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| | |
| | D) CASEMENT WINDOWS AS SHOWN ON PLANS. |
| | |
| | E) FIXED WINDOWS AS SHOWN ON PLANS. |
| | |
| | F) SLIDING WINDOWS AS SHOWN ON PLANS. |
| | |
| | G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED |
| | DESIGN PRESSURES. |
| | |
| | H) FRENCH DOORS AS SHOWN ON PLANS. |
| | |
| | I) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| | |
| | J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T |
| | HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | |
| | K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE. |
| | |
| | L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH |
| | SEC. R905.15 FBC-RESIDENTIAL. COORDINATE WITH ITEM #15 |
| | ABOVE. |
| | |
| | 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | 18-2-PROVIDE PRODUCT APPROVALS, OR INDICATE THAT THEY |
| | WILL BE DEFERRED. |
| | |
| | [FBC AMENDED 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS |
| | SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR |
| | REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE |
| | INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN APPROVED BY THE BUILDING OFFICIAL. |
| | 19- OK |
| | |
| | 20- IMPORTANT: CONTRACTOR TO COORDINATE WITH KEN CONRAD |
| | (CHIEF BUILDING INSPECTOR) FOR INSPECTIONS OF SPECIAL |
| | CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY |
| | AMENDMENTS TO AVOID CONFLICTS/DELAYS. |
| | KEN CONRAD (561)805-6666 OR E-MAIL [email protected] |
| | |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |