| 2018-04-03 14:17:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET E3.0.1 SHOWS A REVISION TO THE MAIN DISCONNECT |
| | AND FEEDER TO PANELS LA/LB. ORIGINAL PLAN SHOWED THE |
| | DISCONNECT ADJACENT TO THE METER WHILE THE NEW PLAN |
| | SHOWS THE DISCONNECT LOCATED ON THE THIRD FLOOR. PLAN |
| | DOES NOT CLEARLY SHOW IF THERE IS ANY OVERCURRENT |
| | PROTECTION ON THE CONDUCTORS AT THE METER. THE SERVICE |
| | DISCONNECTING MEANS SHOULD BE INSTALLED IN A LOCATION |
| | THAT DOES NOT PERMIT UNPROTECTED CONDUCTORS IN THE |
| | BUILDING. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| | 230.70 |
| | |
| | END OF COMMENTS. |
| | |