| Plan Review Notes For Permit 18030590 |
| Permit Number |
18030590 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-22 14:55:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC 107, TOO MANY SHEETS WERE SUBMITTED. | | | SPECIFICATIONS, GENERAL NOTES, ARE NOT REQUIRED FOR AN | | | INTERIOR DEMO PERMIT. MUCH OF THE INFORMATION IS NOT | | | APPLICABLE, AND THE PORTION THAT DEMONSTRATES CODE | | | COMPLIANCE AND IS APPLICABLE SHOULD BE ABLE TO BE | | | CONDENSED ONTO THE PAGE WHICH SHOWS ACTUAL WORK | | | PROPOSED. | | | | | | 2. FBC B 3006, IT APPEARS THAT AN ELEVATOR LOBBY IS | | | REQUIRED. DEMO PLAN PROPOSES TO REMOVE A DOOR FOR THE | | | ELEVATOR LOBBY. REVISE TO RETAIN THE REQUIRED ELEVATOR | | | LOBBY OR REVISE TO STATE WHY AN ELEVATOR LOBBY IS NOT | | | REQUIRED. | | | | | | |
|