| Plan Review Notes For Permit 18030566 |
| Permit Number |
18030566 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-21 10:34:51 | COMMERCIAL ROOFING, SECOND BUILDING REVIEW CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- ROOFING RECOVER DECK NOA 15-0731.14 SUBMITTED | | | EXPIRED ON 05/16/17. NEED TO PROVIDE CURRENT PRODUCT | | | APPROVAL. FAC 61G1520-3.001. | | | | | | 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE | | | REVISED REFERING TO NEW CURRENT PRODUCT APPROVAL AS | | | REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING. | | | | | | 3- RAS 117 CALCULATIONS AND FASTENER WITHDRAWAL | | | RESISTANCE TEST 105 NEED TO HAVE THE ENGINEER'S | | | ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS | | | FOR PUBLIC RECORDS AS REQUIRED BY FAC 61G15-23.001. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|