2018-03-19 15:58:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO PLAN DRAWING SHEETS SUBMITTED WITH THIS
 PERMIT.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND
 APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS.
 (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE
 WITH THE APPLICABLE CODES AND STANDARDS.
 (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF
 CONSTRUCTION DOCUMENTS ON SITE.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PER NFPA 72
  
 7.1 APPLICATION. (SIG-FUN)
 7.1.1 THE DOCUMENTATION OF THE DESIGN, ACCEPTANCE, AND
 COMPLETION OF NEW SYSTEMS REQUIRED UNDER THIS CODE
 SHALL
 COMPLY WITH THE MINIMUM REQUIREMENTS OF THIS CHAPTER.
  
 PLEASE SUBMIT A PLAN SHEET SHOWING ALL PROPOSED OR
 EXISTING LOCATIONS.
  
  
  
  
 2) FOR ANY NEW EQUIPMENT A CIRCUIT DIAGRAM SHALL BE
 SUBMITTED INCLUDING RECALCULATED VOLTAGE.
  
 PER NFPA 72
  
 7.2* MINIMUM REQUIRED DOCUMENTATION. (SIG-FUN)
 7.2.1 WHERE DOCUMENTATION IS REQUIRED BY THE ENFORCING
 AUTHORITY,
 THE FOLLOWING LIST SHALL REPRESENT THE MINIMUM
 DOCUMENTATION
 REQUIRED FOR ALL FIRE ALARM AND EMERGENCY
 COMMUNICATIONS
 SYSTEMS, INCLUDING NEW SYSTEMS AND ADDITIONS OR
 ALTERATIONS TO EXISTING SYSTEMS:
 (1)*WRITTEN NARRATIVE PROVIDING INTENT AND SYSTEM
 DESCRIPTION
 (2) RISER DIAGRAM
 (3) FLOOR PLAN LAYOUT SHOWING LOCATION OF ALL DEVICES
 AND
 CONTROL EQUIPMENT
 (4) SEQUENCE OF OPERATION IN EITHER AN INPUT/OUTPUT
 MATRIX
 OR NARRATIVE FORM
 (5) EQUIPMENT TECHNICAL DATA SHEETS
 (6) MANUFACTURERS PUBLISHED INSTRUCTIONS, INCLUDING
 OPERATION
 AND MAINTENANCE INSTRUCTIONS
 (7) BATTERY CALCULATIONS (WHERE BATTERIES ARE PROVIDED)
 (8) VOLTAGE DROP CALCULATIONS FOR NOTIFICATION
 APPLIANCE CIRCUITS
 (9)*COMPLETED RECORD OF INSPECTION AND TESTING IN
 ACCORDANCE
 WITH 7.6.6 AND 7.8.2
 (10) COMPLETED RECORD OF COMPLETION IN ACCORDANCE WITH
 7.5.6 AND 7.8.2
 (11) COPY OF SITE-SPECIFIC SOFTWARE, WHERE APPLICABLE
 (12) RECORD (AS-BUILT) DRAWINGS
 (13) PERIODIC INSPECTION, TESTING, AND MAINTENANCE
 DOCUMENTATION
 IN ACCORDANCE WITH SECTION 7.6
 (14) RECORDS, RECORD RETENTION, AND RECORD MAINTENANCE
 IN
 ACCORDANCE WITH SECTION 7.7
 7.2.2* THE PERSON RESPONSIBLE FOR SYSTEM DESIGN
 (LAYOUT) SHALL
 BE IDENTIFIED ON THE SYSTEM DESIGN DOCUMENTS.
 7.2.3 ALL FIRE ALARM DRAWINGS SHALL USE SYMBOLS
 DESCRIBED IN
 NFPA 170, STANDARD FOR FIRE SAFETY AND EMERGENCY
 SYMBOLS, OR
 OTHER SYMBOLS ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION.
 7.3 DESIGN (LAYOUT) DOCUMENTATION.
 7.3.1* THE REQUIREMENTS OF SECTION 7.3 SHALL APPLY ONLY
 WHERE
 REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS;
 BY
 OTHER PARTS OF THIS CODE; OR BY PROJECT SPECIFICATIONS
 OR DRAWINGS.
 (SIG-FUN)
  
 PLEASE PROVIDE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL