| Plan Review Notes For Permit 18030550 |
| Permit Number |
18030550 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-14 19:08:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | TRUSS DRAWINGS DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS ARE NOT | | | SIGNED AND SEALED BY THE TRUSS ENGINEER. FS 471 & FAC | | | 61G15-31.003 | | | | | | 2) THE TRUSS PLACEMENT PLAN IS A MIRROR IMAGE OF THE | | | PROPOSED STRUCTURE. SUBMIT TWO SETS OF THE PLACEMENT | | | PLANS THAT MATCH THIS STRUCTURE. FBC 107.2.1 | | | | | | 3) THE FLOOR TRUSS LAYOUT DOES NOT MATCH THE FLOOR | | | FRAMING PLANS THAT WERE SUBMITTED. REVISE SO THAT THEY | | | MATCH. FBC-R802.1.7 | | | | | | 4) THE UPPER ROOF FRAMING PLAN DOES NOT MATCH THE TRUSS | | | PLACEMENT PLAN. REVISE SO THAT THEY MATCH. FBC-R802.1.7 | | | | | | 5) TWO SETS OF FRAMING DETAILS ARE REQUIRED TO BE | | | SUBMITTED FOR THE AREAS THAT WILL BE CONVENTIONALLY | | | FRAMED. FBC-R802..2 & FBC 107.2.1 | | | |
|