2018-04-11 11:38:37****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 RESIDENTIAL (R3) TRUSS PACKAGE SUBMITTAL, SECOND
 BUILDING REVIEW CHECKLIST.
  
 CODE: FBC 5TH EDITION (2014).
  
 4/11/18 THIRD REVIEW
  
 PLAN REVIEW RESPONSE WILL BE ON TOP OF EACH PREVIOUS
 COMMENT.
  
  
 1- NOT ADDRESSED
 ROOF TRUSS LAYOUT DOESN'T MATCH DESIGNER OF RECORD ROOF
 FRAMING PLAN ON SHEET S-3. REVISE AS REQUIRED TO MATCH.
 SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH
 PLANS WILL BE REVISED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 LAYOUTS WERE SUBMITED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 2- NOT ADDRESSED
 SECOND FLOOR TRUSS LAYOUT DOESN'T MATCH DESIGNER OF
 RECORD SECOND FLOOR FRAMING PLAN ON SHEET S-2. REVISE
 AS REQUIRED TO MATCH DESIGNER OF RECORD . SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH
 PLANS WILL BE REVISED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 LAYOUTS WERE SUBMITTED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 3- NOT ADDRESSED
 TRUSSES ARE DESIGNED BASED ON BUILDING EXPOSURE "C".
 DESIGNER OF RECORD DESIGNED STRUCTURE BASED ON BUILDING
 EXPOSURE "D" SEE SHEET S-2 AND S-3. TRUSS ENGINEER TO
 REVISE TRUSSES DESIGN AS REQUIRED TO MATCH DESIGNER OF
 RECORD DESIGN CRITERIA . SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: TRUSS CONNECTORS SPECIFIED BY THE DESIGNER OF
 RECORD WILL BE REVIEWED ONCE TRUSS PACKAGE IS REVISED
 FOR CORRECT EXPOSURE "D".
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 PACKAGE WAS SUBMITTED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 4- ADDRESSED
  
 5- ADDRESSED
  
 6- ADDRESSED
  
  
  
 1- NOT ADDRESSED
 SEE COPY OF COMMENTS BELOW FOR REVISION #18020906. THIS
 COMMENTS ARE RELEVANT TO TRUSS PACKAGE REVIEW COMMENTS
 ABOVE:
 RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THIS REVISION IS FOR CONCRETE ROOF TILES.
 ORIGINALLY, THE HOUSE WAS DESIGNED WITH METAL ROOFING.
 THE DESIGN CRITERIA CONSIDERED FOR THIS HOUSE DIDN'T
 INCLUDE THE ADDITIONAL WEIGHT OF THE CONCRETE TILE. SEE
 DESIGN CRITERIA ON SHEET S-2 AND S-3. DESIGNER OF
 RECORD NEEDS TO REVISE THE DESIGN CRITERIA ACCORDINGLY
 SO THE ROOF TRUSSES ARE DESIGNED FOR THE PROPER
 LOADING. PROVIDE 2 COPIES. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. DESIGNER OF
 RECORD DIDN'T REVISED SHEET S-2 AND S-3. NOTE: REVISION
 FEES WILL APPLY.
  
 IMPORTANT :
 TRUSS PACKAGE IS BEING REVIEWED UNDER SUBMITTAL
 #18030548. SEE THIS SUBMITTAL # FOR COMMENTS.
  
 2- NOT ADDRESSED
  
 DESIGNER OF RECORD TO SPECIFY NEW ROOF TILE FASTENING
 METHOD AS REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS.
 IF USING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF USING ROOF TILE ADHESIVE, THEN PRODUCT
 APPROVAL IS REQUIRED. SEE ROOF TILE NOA FOR LISTED
 ADHESIVE AND SUBMIT 2 COPIES OF THE ADHESIVE PRODUCT
 APPROVAL.
 SEC. 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS
 SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF
 ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER
 CER T I F Y IN G SU I TABI L I T Y FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 4- OWES $51.50 FOR NEW EXTERIOR DOOR NOA NO. 15-0413.12
 SUBMITTED.
  
  