Plan Review Notes
Plan Review Notes For Permit 18030548
Permit Number 18030548
Review Stop B
Sequence Number 2
Notes
Date Text
2018-03-30 11:58:49RESIDENTIAL (R3) TRUSS PACKAGE SUBMITTAL, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ROOF TRUSS LAYOUT DOESN'T MATCH DESIGNER OF RECORD
 ROOF FRAMING PLAN ON SHEET S-3. REVISE AS REQUIRED TO
 MATCH. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH
 PLANS WILL BE REVISED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 LAYOUTS WERE SUBMITED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 2- SECOND FLOOR TRUSS LAYOUT DOESN'T MATCH DESIGNER OF
 RECORD SECOND FLOOR FRAMING PLAN ON SHEET S-2. REVISE
 AS REQUIRED TO MATCH DESIGNER OF RECORD . SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH
 PLANS WILL BE REVISED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 LAYOUTS WERE SUBMITTED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 3- TRUSSES ARE DESIGNED BASED ON BUILDING EXPOSURE "C".
 DESIGNER OF RECORD DESIGNED STRUCTURE BASED ON BUILDING
 EXPOSURE "D" SEE SHEET S-2 AND S-3. TRUSS ENGINEER TO
 REVISE TRUSSES DESIGN AS REQUIRED TO MATCH DESIGNER OF
 RECORD DESIGN CRITERIA . SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: TRUSS CONNECTORS SPECIFIED BY THE DESIGNER OF
 RECORD WILL BE REVIEWED ONCE TRUSS PACKAGE IS REVISED
 FOR CORRECT EXPOSURE "D".
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SAME TRUSS
 PACKAGE WAS SUBMITTED. NOTE: REVISION FEES APPLY IF
 DESIGNER OF RECORD REVISES FRAMING PLANS.
  
 4- TRUSS LAYOUT SHOW THE TRUSS TO TRUSS CONNECTORS AND
 LOCATION. TRUSS ENGINEER TO SIGN AND SEAL THESE PLANS
 AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 5- A) TRUSS ENGINEER TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE ON COVER PAGE AS REQUIRED BY FAC
 61G15-31.003.
  
 B) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION OF THE
 THE BUILDING DESIGNER ON THE COVER PAGE AS REQUIRED BY
 FAC 61G15-31.003.
  
 6- DESIGNER OF RECORD TO REVIEW ALL REVISED TRUSS
 DRAWINGS BEFORE SUBMITTAL TO THIS OFFICE. SEC.
 107.3.4.1 CITY AMENDMENTS.
 IMPORTANT: DESIGNER OF RECORD TO VERIFY THAT ALL TRUSS
 CONNECTORS SPECIFIED ON PLANS WILL MEET THE CALCULATED
 LOADS BY THE TRUSS ENGINEER TO AVOID CONFLICTS OR
 DELAYS. IF CONNECTORS NEED TO BE REVISED, THEN SUBMITT
 THOSE ALONG WITH THE TRUSS DRAWINGS TO AVOID DELAYS.
  
  
 IMPORTANT: NEW COMMENT.
 1- SEE COPY OF COMMENTS BELOW FOR REVISION #18020906.
 THIS COMMENTS ARE RELEVANT TO TRUSS PACKAGE REVIEW
 COMMENTS ABOVE:
  
 RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THIS REVISION IS FOR CONCRETE ROOF TILES.
 ORIGINALLY, THE HOUSE WAS DESIGNED WITH METAL ROOFING.
 THE DESIGN CRITERIA CONSIDERED FOR THIS HOUSE DIDN'T
 INCLUDE THE ADDITIONAL WEIGHT OF THE CONCRETE TILE. SEE
 DESIGN CRITERIA ON SHEET S-2 AND S-3. DESIGNER OF
 RECORD NEEDS TO REVISE THE DESIGN CRITERIA ACCORDINGLY
 SO THE ROOF TRUSSES ARE DESIGNED FOR THE PROPER
 LOADING. PROVIDE 2 COPIES. SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED. DESIGNER OF
 RECORD DIDN'T REVISED SHEET S-2 AND S-3. NOTE: REVISION
 FEES WILL APPLY.
  
 IMPORTANT :
 TRUSS PACKAGE IS BEING REVIEWED UNDER SUBMITTAL
 #18030548. SEE THIS SUBMITTAL # FOR COMMENTS.
  
 2- DESIGNER OF RECORD TO SPECIFY NEW ROOF TILE
 FASTENING METHOD AS REQUIRED BY SEC. 107.2.1.1 CITY
 AMENDMENTS. IF USING SCREWS, THEN SPECIFY SIZE AND
 NUMBER OF SCREWS. IF USING ROOF TILE ADHESIVE, THEN
 PRODUCT APPROVAL IS REQUIRED. SEE ROOF TILE NOA FOR
 LISTED ADHESIVE AND SUBMIT 2 COPIES OF THE ADHESIVE
 PRODUCT APPROVAL.
  
 SEC. 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS
 SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF
 ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER
 CER T I F Y IN G SU I TABI L I T Y FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 4- OWES $51.50 FOR NEW EXTERIOR DOOR NOA NO. 15-0413.12
 SUBMITTED.
  