2018-03-20 13:05:40RESIDENTIAL (R3) TRUSS PACKAGE SUBMITTAL, BUILDING
 REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1- ROOF TRUSS LAYOUT DOESN'T MATCH DESIGNER OF RECORD
 ROOF FRAMING PLAN ON SHEET S-3. REVISE AS REQUIRED TO
 MATCH DESIGNER OF RECORD . SEC. R301.1 FBC-RESIDENTIAL.
  
 2- SECOND FLOOR TRUSS LAYOUT DOESN'T MATCH DESIGNER OF
 RECORD SECOND FLOOR FRAMING PLAN ON SHEET S-2. REVISE
 AS REQUIRED TO MATCH DESIGNER OF RECORD . SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH
 PLANS NEED TO BE REVISED.
  
 3- TRUSSES ARE DESIGNED BASED ON BUILDING EXPOSURE "C".
 DESIGNER OF RECORD DESIGNED STRUCTURE BASED ON BUILDING
 EXPOSURE "D" SEE SHEET S-2 AND S-3. TRUSS ENGINEER TO
 REVISE TRUSSES DESIGN AS REQUIRED TO MATCH DESIGNER OF
 RECORD DESIGN CRITERIA . SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: TRUSS CONNECTORS SPECIFIED BY THE DESIGNER OF
 RECORD WILL BE REVIEWED ONCE TRUSS PACKAGE IS REVISED
 FOR CORRECT EXPOSURE "D".
  
 4- TRUSS LAYOUT SHOW THE TRUSS TO TRUSS CONNECTORS AND
 LOCATION. TRUSS ENGINEER TO SIGN AND SEAL THESE PLANS
 AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 5- TRUSS ENGINEER TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE AND TITLE BLOCK WITH ALL HIS INFORMATION ON
 ALL TRUSS DRAWINGS AS REQUIRED BY FAC 61G15-23.001.
 NOTE: TRUSS ENGINEER MAY USE A COVER INDEX SHEET IF ALL
 THE REQUIRED INFORMATION BY FAC 61G15-31.003 IS
 PROVIDED.
  
 6- DESIGNER OF RECORD TO REVIEW ALL REVISED TRUSS
 DRAWINGS BEFORE SUBMITAL TO THIS OFFICE. SEC. 107.3.4.1
 CITY AMENDMENTS.
 IMPORTANT: DESIGNER OF RECORD TO VERIFY THAT ALL TRUSS
 CONNECTORS SPECIFIED ON PLANS WILL MEET THE CALCULATED
 LOADS BY THE TRUSS ENGINEER TO AVOID CONFLICTS OR
 DELAYS. IF CONNECTORS NEED TO BE REVISED, THEN SUBMITT
 THOSE ALONG WITH THE TRUSS DRAWINGS TO AVOID DELAYS.
  
 NOTE: DESIGNER OF RECORD TO REVIEW NOTE #2 ON TRUSS
 DRAWINGS SUBMITTED. EVEN THOUGH THE HOUSE IS DESIGNED
 TO RECEIVE LIGHT WEIGHT METAL ROOFING, IT MAY BE AN
 IMPEDIMENT FOR OWNER TO USE A ROOFING MATERIAL OTHER
 THAN METAL ROOFING. ( JUST A THOUGHT).
  
  
 **** DESIGNER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO HELP THE REVIEW PROCESS.
  