| Date |
Text |
| 2018-03-20 13:05:40 | RESIDENTIAL (R3) TRUSS PACKAGE SUBMITTAL, BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- ROOF TRUSS LAYOUT DOESN'T MATCH DESIGNER OF RECORD |
| | ROOF FRAMING PLAN ON SHEET S-3. REVISE AS REQUIRED TO |
| | MATCH DESIGNER OF RECORD . SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 2- SECOND FLOOR TRUSS LAYOUT DOESN'T MATCH DESIGNER OF |
| | RECORD SECOND FLOOR FRAMING PLAN ON SHEET S-2. REVISE |
| | AS REQUIRED TO MATCH DESIGNER OF RECORD . SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: COORDINATE WITH DESIGNER OF RECORD TO SEE WHICH |
| | PLANS NEED TO BE REVISED. |
| | |
| | 3- TRUSSES ARE DESIGNED BASED ON BUILDING EXPOSURE "C". |
| | DESIGNER OF RECORD DESIGNED STRUCTURE BASED ON BUILDING |
| | EXPOSURE "D" SEE SHEET S-2 AND S-3. TRUSS ENGINEER TO |
| | REVISE TRUSSES DESIGN AS REQUIRED TO MATCH DESIGNER OF |
| | RECORD DESIGN CRITERIA . SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: TRUSS CONNECTORS SPECIFIED BY THE DESIGNER OF |
| | RECORD WILL BE REVIEWED ONCE TRUSS PACKAGE IS REVISED |
| | FOR CORRECT EXPOSURE "D". |
| | |
| | 4- TRUSS LAYOUT SHOW THE TRUSS TO TRUSS CONNECTORS AND |
| | LOCATION. TRUSS ENGINEER TO SIGN AND SEAL THESE PLANS |
| | AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC |
| | 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL |
| | CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING. |
| | |
| | 5- TRUSS ENGINEER TO PROVIDE ORIGINAL SEAL AND |
| | SIGNATURE AND TITLE BLOCK WITH ALL HIS INFORMATION ON |
| | ALL TRUSS DRAWINGS AS REQUIRED BY FAC 61G15-23.001. |
| | NOTE: TRUSS ENGINEER MAY USE A COVER INDEX SHEET IF ALL |
| | THE REQUIRED INFORMATION BY FAC 61G15-31.003 IS |
| | PROVIDED. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW ALL REVISED TRUSS |
| | DRAWINGS BEFORE SUBMITAL TO THIS OFFICE. SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | IMPORTANT: DESIGNER OF RECORD TO VERIFY THAT ALL TRUSS |
| | CONNECTORS SPECIFIED ON PLANS WILL MEET THE CALCULATED |
| | LOADS BY THE TRUSS ENGINEER TO AVOID CONFLICTS OR |
| | DELAYS. IF CONNECTORS NEED TO BE REVISED, THEN SUBMITT |
| | THOSE ALONG WITH THE TRUSS DRAWINGS TO AVOID DELAYS. |
| | |
| | NOTE: DESIGNER OF RECORD TO REVIEW NOTE #2 ON TRUSS |
| | DRAWINGS SUBMITTED. EVEN THOUGH THE HOUSE IS DESIGNED |
| | TO RECEIVE LIGHT WEIGHT METAL ROOFING, IT MAY BE AN |
| | IMPEDIMENT FOR OWNER TO USE A ROOFING MATERIAL OTHER |
| | THAN METAL ROOFING. ( JUST A THOUGHT). |
| | |
| | |
| | **** DESIGNER OF RECORD TO PROVIDE RESPONSE LETTER |
| | ADDRESSING EACH COMMENT TO HELP THE REVIEW PROCESS. |
| | |