| 2018-03-21 16:24:39 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE PLAN BASED ON THE 2017 FBC 6TH ED. |
| | 2. DESIGNER TO PRINT NAME AND SIGN PLAN. |
| | 3. ALL SUBMITTAL DOCUMMENTS SHALL BE IN DUPLICATE. |
| | 4. ADVISORY ONLY - HANDRAILS SHALL COMPLY WITH FBC |
| | R311.7.8. |
| | |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 |
| | FLORIDA BUILDING CODE, 6TH EDITION. |
| | |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | R311.7.8 HANDRAILS. |
| | HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF |
| | EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR |
| | MORE RISERS. R311.7.8. |
| | HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED |
| | PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF |
| | RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM) |
| | AND NOT MORE THAN 38 INCHES (965 MM). R311.7.8.1 HEIGHT |
| | |
| | R312.1.3 OPENING LIMITATIONS. |
| | REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE |
| | WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH |
| | ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN |
| | DIAMETER. |
| | |
| | R311.7.9 ILLUMINATION. |
| | ALL STAIRS SHALL BE PROVIDED WITH ILLUMINATION IN |
| | ACCORDANCE WITH SECTION R303.6. |
| | |
| | 453.8.8.6 |
| | EXTERIOR STAIRS, BALCONIES, RAMPS, AND UPPER LEVEL |
| | CORRIDORS AROUND THE PERIMETER OF BUILDINGS SHOULD HAVE |
| | OPEN-TYPE HANDRAILS OR OTHER ARCHITECTURAL FEATURES TO |
| | ALLOW SURVEILLANCE. |
| | |
| | |