Plan Review Notes
Plan Review Notes For Permit 18030477
Permit Number 18030477
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-13 17:08:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLANS INDICATE THEY ARE AS-BUILT;
 HOWEVER, THERE IS NO INDICATORS OR REVISION CLOUDS AS
 TO WHAT IS AS-BUILT.
  
 PER NFPA 1, CHAPTER 1, ADMINISTRATION
  
 1.14 PLAN REVIEW.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR
 REVIEW AND APPROVAL TO ILLUSTRATE CORRECTIONS OR
 MODIFICATIONS
 NECESSITATED BY FIELD CONDITIONS OR OTHER REVISIONS TO
 APPROVED
 PLANS.
  
 PLEASE PROVIDE CLOUDS AND OR SOECIFIC NARRATIVE AS TO
 WHAT WAS AS-BUILT.
  
  
 2) IF THE ENTIRE LAYOUT IS AS-BUILT, PLEASE PROVIDE THE
 APPLICABLE HYDRAULIC CALCULATIONS, ALL EQUIPMENT
 SPECIFICATION SHEETS, AND RELATED DOCUMENTS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  