| Plan Review Notes For Permit 18030471 |
| Permit Number |
18030471 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-14 11:59:18 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) IF APPLICABLE TO THIS PROJECT, THE ACTIVATION OF A | | | DUCT DETECTOR SHALL SEND A SUPERVISORY SIGNAL, NOT A | | | FULL ALARM. | | | | | | NFPA 90A | | | | | | 6.4.3* FUNCTION. | | | 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 | | | SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON | | | DETECTING THE PRESENCE OF SMOKE. | | | | | | 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING | | | DAMPERS OR FOR HEATING, VENTILATING, AND | | | AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED | | | TO ACTIVATE THE BUILDING EVACUATION ALARM. | | | | | | NFPA 72 | | | | | | 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC | | | SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|