| Plan Review Notes For Permit 18030464 |
| Permit Number |
18030464 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-21 15:20:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THERE IS A PERMIT #18020529 THAT WAS ISSUED TO REPLACE | | | THE EXISTING CAST IRON SEWER PIPES WITH PVC. IT APPEARS | | | THAT THIS PERMIT IS FOR REPLACING THE CONCRETE THAT WAS | | | CUT AND REMOVED TO ACCESS THE BUILDING DRAIN AND SEWER. | | | | | | 1) PROVIDE TWO SETS OF A FLOOR PLAN THAT SHOWS THE | | | DIMENSIONS AND THICKNESS OF THE CONCRETE THAT IS BEING | | | INSTALLED. FBC-R 606.1 | | | | | | 2) SHOW COMPLIANCE WITH FBC-R 318.1 FOR TERMITE | | | PROTECTION. | | | | | | 3) SHOW COMPLIANCE WITH FBC-R506.2.3 FOR A VAPOR | | | RETARDER (6-MIL POLYETHYLENE). | | | | | | 4) SHOW COMPLIANCE WITH FBC-R506.2.4.2 WHICH REQUIRES | | | FIBER MESH CONCRETE OR WELDED WIRE REINFORCEMENT WIRE | | | TO CONTROL CRACKING. | | | | | | 5) IN ORDER TO PREVENT SETTLEMENT OF THE PATCHED AREAS, | | | PROVIDE DETAILS ON DOWELING INTO THE EXISTING CONCRETE | | | PER ACI 332. FBC-R506.1 | | | | | | | | | | | | |
|