2018-04-09 13:11:231ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #18030448
 4/9/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW AC CLOSET DOOR SHALL BE NON-COMBUSTIBLE PER
 SECTION 602.2.1.
  
 2) REFER TO SECTION 809.1 AND 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PLEASE PROVIDE THE SUPPLY CFMS AT EACH DIFFUSER
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  