Plan Review Notes
Plan Review Notes For Permit 18030448
Permit Number 18030448
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-21 17:08:341ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 602
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 3. SHT. P.1 UNDER PLUMB FIXTURE SCHEDULE IT LIST THE
 MIAMI DADE CODE THAT DOES NOT APPLY TO THIS JOB,.ALL
 PLUMBING FIXTURES AND PIPING SHALL COMPLY WITH FBC PL
 2017 6TH EDITION
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  