Plan Review Notes For Permit 18030448
Permit Number 18030448
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-14 16:34:10 
  
  
 1) STAIRS INDICATED AT DOOR D 102 DO NOT APPEAR TO MEET
 THE REQUIRMENTS OF NFPA 101.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS
  
 38.2.2.3 STAIRS.
 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE
 SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.2.1.2.
  
 7.2.2.3.6* DIMENSIONAL UNIFORMITY.
 7.2.2.3.6.1 VARIATION IN EXCESS OF 3?16 IN. (4.8 MM) IN
 THE SIZES OF
 ADJACENT TREAD DEPTHS OR IN THE HEIGHT OF ADJACENT
 RISERS SHALL BE
 PROHIBITED, UNLESS OTHERWISE PERMITTED IN 7.2.2.3.6.3.
 7.2.2.3.6.2 THE VARIATION BETWEEN THE SIZES OF THE
 LARGEST AND SMALLEST
 RISER OR BETWEEN THE LARGEST AND SMALLEST TREAD DEPTHS
 SHALL NOT EXCEED ?
 IN. (9.5 MM) IN ANY FLIGHT.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  