Plan Review Notes
Plan Review Notes For Permit 18030447
Permit Number 18030447
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-15 12:04:131ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASTE ARM FOR THE SINKS SHALL BE VENTED WITH A
 AIR ADMITTANCE VALVE OR REVENTED BACK TO THE VENT
 STACK. IT APPEARS THAT YOU HAVE A DEVELOPED LENGTH OF
 ABOUT 35', THE MAX YOU CAN RUN A 3" WASTE ARM FROM THE
 VENT TO THE FIXTURE TRAP IS 12' BUSHING IT DOWN TO 2"
 DOES NOT EXTEND THAT LENGTH YOUR DEVELOPED LENGTH WOULD
 BE FROM THE VERTICAL STACK TO THE LAST FIXTURE TRAP.
 FBC PL 909.1 AND TABLE 909.1 AND 901.2.1
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 3. THE LAVATORY AND TOILET ARE MISSING FROM THE WATER
 ISOMETRIC IF THEY ARE EXISTING TO REMAIN SHOW ON
 ISOMETRIC AND MARK EXISTING THEY SHALL BE CODE
 COMPLIANT TO CURRENT CODE. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 6. SHT. A2 UNDER TOILET FIXTURE SPECIFICATIONS #8 LIST
 A WATER FOUNTAIN IT IS NOT SHOWN ON THE PLUMBING
 DRAWINGS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  