| Date |
Text |
| 2018-03-14 15:49:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) TWO EXITS ARE INDICATED ON SHEET A 3 AND E 1. THE |
| | DOOR TO THE BATHROOM IS OUT SWINGING OBSTRUCTUNG THE |
| | EXIT TRAVEL PATH. |
| | |
| | ONE EXIT MAY BE ALL THAT IS REQUIRED IF IT MEETS THE |
| | REQUIRMENTS LISTED BELOW. IF SO, THE EXIT SIGN BY THE |
| | BATHROOM MAY BE REMOVED AND THE BATHROOM DOOR REMAIN. |
| | |
| | PLEASE REVIEW ALONG WITH BUILDING COMMENTS. |
| | |
| | 38.2 MEANS OF EGRESS REQUIREMENTS. |
| | 38.2.1 GENERAL. |
| | 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| | WITH CHAPTER 7 AND |
| | THIS CHAPTER. |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL |
| | BE PERMITTED TO |
| | INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS COMMON |
| | PATHS OF TRAVEL BY 38.2.5.3. |
| | 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| | AREA WITH A TOTAL |
| | OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| | THE LEVEL OF EXIT |
| | DISCHARGE FOR THE BUILDING. |
| | (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| | INCLUDING TRAVEL WITHIN |
| | THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| | (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| | 38.2.4.3(2) SHALL BE ON THE |
| | SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| | SUCH STAIRS SHALL |
| | NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| | FOLLOWING |
| | ALSO SHALL APPLY: |
| | (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| | ENCLOSURES TO |
| | SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| | NO |
| | DOOR OPENINGS THEREIN. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| | FT (4570 |
| | MM) VERTICAL TRAVEL LIMITATION. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |