Plan Review Notes
Plan Review Notes For Permit 18030438
Permit Number 18030438
Review Stop E
Sequence Number 1
Notes
Date Text
2018-03-13 15:56:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE STATED ON REVISION FORM FOR THE ADDITIONAL
 WORK SHOWN ON PLAN APPEARS LOW. PROVIDE COPY OF SIGNED
 CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL
 MATERIALS AND LABOR. FBC 109.3
 2. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. FBC
 110.3
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. INCLUDE LOAD CALCULATION FOR PANEL IF THE
 LOAD IS TO BE INCREASED FOR WATER HEATER. NEC 210.8,
 210.12, 215.5, 220, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  