| 2018-03-13 15:56:01 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. VALUE STATED ON REVISION FORM FOR THE ADDITIONAL |
| | WORK SHOWN ON PLAN APPEARS LOW. PROVIDE COPY OF SIGNED |
| | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL |
| | MATERIALS AND LABOR. FBC 109.3 |
| | 2. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. FBC |
| | 110.3 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. INCLUDE LOAD CALCULATION FOR PANEL IF THE |
| | LOAD IS TO BE INCREASED FOR WATER HEATER. NEC 210.8, |
| | 210.12, 215.5, 220, 408.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |