| Plan Review Notes For Permit 18030408 |
| Permit Number |
18030408 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-13 16:07:27 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEEDS ENGINEERS SEAL CONTRACTOR LIMITED TO 250VOLTS | | | | | | VALUE FOR WORK TO LOW. VALUE IS BASED ON TOTAL JOB | | | PACKAGE LABOR MATERIALS ECT, ECT. | | | | | | RISER AND PANEL SCHEDULE DON'T MATCH | | | | | | 100A CIRCUIT NEEDS A #8 EQUIPMENT GROUND | | | | | | 40A CIRCUIT NEEDS A #10 EQUIPMENT GROUND | | | | | | SUBMIT CUT SHEETS FOR OUTLETS TO BE SUPPLIED. | | | | | | |
|