2018-03-13 16:07:27FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEEDS ENGINEERS SEAL CONTRACTOR LIMITED TO 250VOLTS
  
 VALUE FOR WORK TO LOW. VALUE IS BASED ON TOTAL JOB
 PACKAGE LABOR MATERIALS ECT, ECT.
  
 RISER AND PANEL SCHEDULE DON'T MATCH
  
 100A CIRCUIT NEEDS A #8 EQUIPMENT GROUND
  
 40A CIRCUIT NEEDS A #10 EQUIPMENT GROUND
  
 SUBMIT CUT SHEETS FOR OUTLETS TO BE SUPPLIED.
  
  