Plan Review Notes
Plan Review Notes For Permit 18030381
Permit Number 18030381
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-24 08:28:222ND REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17
 PERMIT #18030381
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EQUIPMENT IDENTIFICATION NUMBERS ON THE KITCHEN
 PLANS ARE TOO SMALL AND TOO FAINT TO READ OR TO BE
 SCANNED FOR PUBLIC RECORD. PLEASE PROVIDE CLEAR LEGIBLE
 PLANS PER SECTION 107.2.1 WPB AMENDMENTS.
  
 2) IF THE OVENS AND OTHER COOKING EQUIPMENT UNDER THE
 HOODS ARE GAS-FIRED, THEN AS PREVIOUSLY REQUESTED,
 PROVIDE COMBUSTION AIR CALCULATIONS PER SECTION 304
 FBC-17 FUEL GAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  