| Date |
Text |
| 2018-03-22 15:55:39 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. T-1.0 UNDER DESIGN CODES ACCESSIBILITY SHALL |
| | COMPLY WITH FBC ACC 6TH EDITION 2017 NOT THE 5TH |
| | EDITION. PLEASE CORRECT ON PLAN SHEET. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 2. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE |
| | FOR THE TOILET AND LAVATORY IN THE ACCESSIBLE |
| | BATHROOMS. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 3. SHT. K-1.0-4.0 THERE ARE 2 EXTRA BATHROOMS SHOWN ON |
| | THE BACK WALL OF THE SPACE NEXT TO THE DOOR THEY ARE |
| | NOT SHOWN ON ANY OTHER SHEETS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 4. THE EQUIPMENT PLAN IS UNCLEAR AND NEEDS TO BE |
| | ENLARGED TO READ IT CLEARLY TO DETERMINE CODE |
| | COMPLIANCE THE SCALE IS REQUIRED TO BE 1/8" FT . PER |
| | WPB AMEND TO FBC 107.2.1.3 |
| | |
| | 5. PLEASE PROVIDE SIZING CALCULATIONS ON THE EXISTING |
| | GREASE INTERCEPTOR TO INCLUDE EXISTING LOAD AND THE NEW |
| | LOAD TO DETERMINE IF EXISTING IS LARGE ENOUGH TO HANDLE |
| | THE ADDITIONAL LOAD. PER FBC PL 1003.2 |
| | |
| | 6. WHO IS RESPONSIBLE FOR THE MAINTENANCE OF THE |
| | EXISTING GREASE INTERCEPTOR AND HOW OFTEN IS IT PUMPED |
| | OUT. PROVIDE LETTER FROM PROPERTY OWNER. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 7. PRIOR TO FINAL INSPECTION THE EXISTING INTERCEPTOR |
| | WILL NEED TO BE CERTIFIED BY UTILITIES DEPARTMENT TO BE |
| | IN GOOD WORKING ORDER PLEASE CONTACT JEFFERY ODOMS WPB |
| | UTILITIES PH 561-822-2172 |
| | |
| | 8. SHT. P-1.1 NOTE #4 THE CIVIL SHEET SHOWING LOCATION |
| | AND SIZE OF THE EXISTING GREASE INTERCEPTOR IS NOT IN |
| | THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 9. SHT. P 4.0 THERE IS A NOTE AT THE BOTTOM OF THE PAGE |
| | REQUIERING A BOOSTER PUMP ON THE FILTER SYSTEM PLEASE |
| | SHOW ON RISER DETAIL AND PROVIDE MANUFACTURE |
| | SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT P-0.1 NOTE #1 THE CURRENT CODE IS THE FBC PL |
| | 6TH EDITION 2017 PLEASE CORRECT ON PLAN. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |