2018-03-22 15:55:391ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. T-1.0 UNDER DESIGN CODES ACCESSIBILITY SHALL
 COMPLY WITH FBC ACC 6TH EDITION 2017 NOT THE 5TH
 EDITION. PLEASE CORRECT ON PLAN SHEET. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE
 FOR THE TOILET AND LAVATORY IN THE ACCESSIBLE
 BATHROOMS. PER FBC ACC 604.3.1, 606.2
  
 3. SHT. K-1.0-4.0 THERE ARE 2 EXTRA BATHROOMS SHOWN ON
 THE BACK WALL OF THE SPACE NEXT TO THE DOOR THEY ARE
 NOT SHOWN ON ANY OTHER SHEETS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE EQUIPMENT PLAN IS UNCLEAR AND NEEDS TO BE
 ENLARGED TO READ IT CLEARLY TO DETERMINE CODE
 COMPLIANCE THE SCALE IS REQUIRED TO BE 1/8" FT . PER
 WPB AMEND TO FBC 107.2.1.3
  
 5. PLEASE PROVIDE SIZING CALCULATIONS ON THE EXISTING
 GREASE INTERCEPTOR TO INCLUDE EXISTING LOAD AND THE NEW
 LOAD TO DETERMINE IF EXISTING IS LARGE ENOUGH TO HANDLE
 THE ADDITIONAL LOAD. PER FBC PL 1003.2
  
 6. WHO IS RESPONSIBLE FOR THE MAINTENANCE OF THE
 EXISTING GREASE INTERCEPTOR AND HOW OFTEN IS IT PUMPED
 OUT. PROVIDE LETTER FROM PROPERTY OWNER. PER WPB AMEND
 TO FBC 107.2.1
  
 7. PRIOR TO FINAL INSPECTION THE EXISTING INTERCEPTOR
 WILL NEED TO BE CERTIFIED BY UTILITIES DEPARTMENT TO BE
 IN GOOD WORKING ORDER PLEASE CONTACT JEFFERY ODOMS WPB
 UTILITIES PH 561-822-2172
  
 8. SHT. P-1.1 NOTE #4 THE CIVIL SHEET SHOWING LOCATION
 AND SIZE OF THE EXISTING GREASE INTERCEPTOR IS NOT IN
 THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 9. SHT. P 4.0 THERE IS A NOTE AT THE BOTTOM OF THE PAGE
 REQUIERING A BOOSTER PUMP ON THE FILTER SYSTEM PLEASE
 SHOW ON RISER DETAIL AND PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT P-0.1 NOTE #1 THE CURRENT CODE IS THE FBC PL
 6TH EDITION 2017 PLEASE CORRECT ON PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  