Plan Review Notes
Plan Review Notes For Permit 18030381
Permit Number 18030381
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-19 11:37:451ST REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17
 PERMIT #18030381
 3/19/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.0: THE PLAN SHOWS RECIRCULATION OF AIR
 FROM THE KITCHEN INTO THE RETAIL SALES/SEATING AREA
 WHICH IS PROHIBITED PER TABLE 403.1.1 FOOTNOTE B.
  
 2) M-2.0: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE
 CALCULATIONS FOR THE REQUIRED REPLACEMENT AIR FOR THE
 KITCHEN EXHAUST SYSTEMS- SEE SECTION 508.1.2.
  
 3) ADVISORY: THE KITCHEN EXHAUST HOODS ARE UNDER
 SEPARATE PERMITS HOWEVER IT IS NECESSARY THAT THE MAIN
 PLAN IS BEING DESIGNED IN COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE- FBC-17 MECHANICAL, AND
 SECTION C403.2.8 FBC-17 ENERGY CONSERVATION. PLEASE
 SHOW COMPLIANCE.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES IN ACCORDANCE WITH SECTION
 304 FBC-17 FUEL GAS. PLEASE INDICATE ON THE PLAN HOW
 THE COMBUSTION AIR IS BEING PROVIDED.
  
 5) SHEETS K-1.0- K-4.0: PLEASE PROVIDE ENLARGED PLANS
 FOR THE TWO KITCHEN COOKING LINES SO THAT THE
 APPLIANCES UNDER THE HOODS ARE EASILY IDENTIFIED.
 PLEASE NOTE THE EQUIPMENT LISTS IS INDICATING A FRYER
 WHICH REQUIRES A GREASE HOOD.
  
 6) PROVIDE COMPLETE WINDLOAD ENGINEERING FOR
 INSTALLATION OF THE RTU INCLUDING THE STRUCTURAL ROOF
 OPENING, THE CURB ATTACHMENT TO THE STRUCTURE, AND THE
 RTU ATTACHMENT TO THE CURB- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719