| 2018-03-19 11:37:45 | 1ST REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION |
| | CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17 |
| | PERMIT #18030381 |
| | 3/19/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.0: THE PLAN SHOWS RECIRCULATION OF AIR |
| | FROM THE KITCHEN INTO THE RETAIL SALES/SEATING AREA |
| | WHICH IS PROHIBITED PER TABLE 403.1.1 FOOTNOTE B. |
| | |
| | 2) M-2.0: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE |
| | CALCULATIONS FOR THE REQUIRED REPLACEMENT AIR FOR THE |
| | KITCHEN EXHAUST SYSTEMS- SEE SECTION 508.1.2. |
| | |
| | 3) ADVISORY: THE KITCHEN EXHAUST HOODS ARE UNDER |
| | SEPARATE PERMITS HOWEVER IT IS NECESSARY THAT THE MAIN |
| | PLAN IS BEING DESIGNED IN COMPLIANCE WITH SECTION |
| | 508.1.1 MAKEUP AIR TEMPERATURE- FBC-17 MECHANICAL, AND |
| | SECTION C403.2.8 FBC-17 ENERGY CONSERVATION. PLEASE |
| | SHOW COMPLIANCE. |
| | |
| | 508.1.1 MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | |
| | C403.2.8 KITCHEN EXHAUST SYSTEMS. |
| | REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST |
| | HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE |
| | HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR |
| | DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF |
| | THE FOLLOWING: |
| | 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE |
| | HEATING OR COOLING LOAD. |
| | 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER |
| | AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS |
| | CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT |
| | REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS |
| | RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION |
| | OF ADJACENT SPACES. |
| | |
| | 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES IN ACCORDANCE WITH SECTION |
| | 304 FBC-17 FUEL GAS. PLEASE INDICATE ON THE PLAN HOW |
| | THE COMBUSTION AIR IS BEING PROVIDED. |
| | |
| | 5) SHEETS K-1.0- K-4.0: PLEASE PROVIDE ENLARGED PLANS |
| | FOR THE TWO KITCHEN COOKING LINES SO THAT THE |
| | APPLIANCES UNDER THE HOODS ARE EASILY IDENTIFIED. |
| | PLEASE NOTE THE EQUIPMENT LISTS IS INDICATING A FRYER |
| | WHICH REQUIRES A GREASE HOOD. |
| | |
| | 6) PROVIDE COMPLETE WINDLOAD ENGINEERING FOR |
| | INSTALLATION OF THE RTU INCLUDING THE STRUCTURAL ROOF |
| | OPENING, THE CURB ATTACHMENT TO THE STRUCTURE, AND THE |
| | RTU ATTACHMENT TO THE CURB- SECTION 301.15 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |