2018-03-23 15:06:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE ALL
 LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. BASED
 ON THE INFORMATION PROVIDED CURRENTLY, B? IS SHOWN WITH
 A TOTAL OF 413 AMPS, WHICH EXCEEDS THE CAPACITY OF THE
 WIRE AND OF THE DISCONNECT. PROVIDE CORRECTION AS
 NEEDED. NEC 215.2, 220, 408.30
 2. ALL RECEPTACLE OUTLETS IN KITCHEN/PREP AREAS REQUIRE
 GFCI PROTECTION, NOT JUST THOSE THAT ARE COUNTERTOP
 RECEPTACLES. PROVIDE CORRECTION. NEC 210.8
 3. PROVIDE BLOCK NOTE STATING SIGNS REQUIRE A SEPARATE
 PERMIT. FBC 107.2.1
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  