2018-03-28 06:52:351) SHT. A0.00 - BUILDING CODE CHECKLIST - THIS PROJECT
 SHALL BE DESIGNED UNDER THE 2017 FBC, NOT THE 2014 AS
 NOTED ON THE PLANS.
 2) ROOM # 953 - GALLEY - SHT.A4.10 - THE BREAK ROOM
 SINK SHALL COMPLY WITH THE 2017FBC-ACCESS. SEC.606.3.
 THE TOP OF THE COUNTER FROM THE FINISH FLOOR SHALL BE A
 MAXIMUM OF 34 INCHES. SHOW THIS ON THE PLAN.WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) SUBMIT A SANITARY RISER FOR THE GALLEY SINK,
 DISHWASHER.
 4) SUBMIT A WATER RISER FOR THE GALLEY SINK,
 DISHWASHER, REFRIGERATOR ( IF IT HAS A WATER OR ICE
 DISPENSER), THE CCOFFEE MAKERS & WATER/ICE DISPENSER.)
 5) THE REFRIGERATOR, COFFEE MAKERS AND ICE/WATER
 DISPENSER SHALL BE EQUIPPED WITH BACKFLOW PREVENTERS
 PER 2017 FBC-PLUMBING SECS. 608.3, 608.16.10.
 6) AIR ARRESTORS SHALL BE INSTALLED ON ALL QUICK
 CLOSING VALVES PER 2017 FBC-PLUMBING SEC.604.9
 (DISHWASHER, REFRIGERATOR, WATER/ICE DISPENSER.
 7) INDICATE THE LEVEL OF ALTERATION ON THE PLAN IN
 ACCORDANCE WITH THE 2017 FBC-EXISTING BUILDING CODE
 SEC.301.1.
 8) THE GALLEY SINK SHALL BE SUPPLIED WITH HOT WATER.
 2017 FBC-PLUMBING SEC. 607.1.
  