| Plan Review Notes For Permit 18030356 |
| Permit Number |
18030356 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-28 06:52:35 | 1) SHT. A0.00 - BUILDING CODE CHECKLIST - THIS PROJECT | | | SHALL BE DESIGNED UNDER THE 2017 FBC, NOT THE 2014 AS | | | NOTED ON THE PLANS. | | | 2) ROOM # 953 - GALLEY - SHT.A4.10 - THE BREAK ROOM | | | SINK SHALL COMPLY WITH THE 2017FBC-ACCESS. SEC.606.3. | | | THE TOP OF THE COUNTER FROM THE FINISH FLOOR SHALL BE A | | | MAXIMUM OF 34 INCHES. SHOW THIS ON THE PLAN.WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 3) SUBMIT A SANITARY RISER FOR THE GALLEY SINK, | | | DISHWASHER. | | | 4) SUBMIT A WATER RISER FOR THE GALLEY SINK, | | | DISHWASHER, REFRIGERATOR ( IF IT HAS A WATER OR ICE | | | DISPENSER), THE CCOFFEE MAKERS & WATER/ICE DISPENSER.) | | | 5) THE REFRIGERATOR, COFFEE MAKERS AND ICE/WATER | | | DISPENSER SHALL BE EQUIPPED WITH BACKFLOW PREVENTERS | | | PER 2017 FBC-PLUMBING SECS. 608.3, 608.16.10. | | | 6) AIR ARRESTORS SHALL BE INSTALLED ON ALL QUICK | | | CLOSING VALVES PER 2017 FBC-PLUMBING SEC.604.9 | | | (DISHWASHER, REFRIGERATOR, WATER/ICE DISPENSER. | | | 7) INDICATE THE LEVEL OF ALTERATION ON THE PLAN IN | | | ACCORDANCE WITH THE 2017 FBC-EXISTING BUILDING CODE | | | SEC.301.1. | | | 8) THE GALLEY SINK SHALL BE SUPPLIED WITH HOT WATER. | | | 2017 FBC-PLUMBING SEC. 607.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|