Plan Review Notes
Plan Review Notes For Permit 18030342
Permit Number 18030342
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-15 17:55:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT WAS PERMITTED UNDER THE 2014 FBC FIFTH
 EDITION AND THE TRUSS PLACEMENT PLANS AND TRUSS
 DRAWINGS THAT WERE SUBMITTED ARE FOR THE 2017 FBC SIXTH
 EDITION. REVISE TRUSS DOCUMENTS TO REFERENCE THE 2014
 FBC FIFTH EDITION.
  
 2) THE TRUSS TRUSS PLACEMENT PLANS AND TRUSS DRAWINGS
 ARE REQUIRED TO HAVE THE TRUSS DESIGN ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003 THE
 TRUSS PLACEMENT PLANS ARE NOT SIGNED AND SEALED AND THE
 TRUSS DRAWINGS HAVE A COPIED SIGNATURE.
  
 3) THE STRUCTURAL ENGINEER OF RECORD IS REQUIRED TO
 REVIEW THE TRUSS DOCUMENTS FOR COMFORMANCE TO HIS
 REQUIREMENTS IN ACCORDANCE WITH FAC CHAPTER
 61G15-30.005. PROVIDE TWO SETS OF TRUSS DOCUMENTS WITH
 THE STRUCTURAL ENGINEER OF RECORD'S APPROVED SHOP
 REVIEW STAMP. FBC 107.2.1