| 2018-05-24 13:42:05 | 3RD REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #18030309 |
| | 5/24/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IN RESPONSE TO THE ISSUE OF THE O/A DUCT LOCATED IN |
| | THE INTERIOR EXIT STAIRWAY EXTENSION THE EOR IS |
| | PROPOSING THAT THE EXISTING FIRE-RATED CEILING IN THE |
| | EXTENSION BE REMOVED AND A 2HR. RATED FIRE WRAP TO BE |
| | APPLIED TO THE DUCT. REMOVAL OF THE CEILING HOWEVER |
| | DOES NOT SOLVE THE PROBLEM OF THE DUCT AND POSSIBLY |
| | OTHER PROHIBITED ELECTRICAL CONDUITS, PLUMBING OR FIRE |
| | SPRINKLER PIPINGS, |
| | |
| | MECHANCIAL COMPONENTS ETC. FROM BEING LOCATED IN THE |
| | STAIRWAY EXTENSION, AND NOT FOR THE PURPOSE OF SERVING |
| | THE STAIRWAY EXTENSION. MORE INFORMATION AS TO WHAT MEP |
| | SYSTEMS ARE LOCATED IN THE EXTENSION IS REQUIRED. |
| | PLEASE NOTE THAT THE PROJECT HAS BEEN DETERNINED TO BE |
| | LEVEL II ALTERATION BY THE ARCHITECT. AND, IN |
| | ACCORDANCE WITH SECTIONS 701.2 AND 801.2 , THE BUILDING |
| | SHALL |
| | |
| | NOT BE ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE |
| | OR ENERGY EFFICIENT THAN IT'S EXISTING CONDITION. |
| | REMOVAL OF THE CEILING APPARENTLY WOULD MAKE THE |
| | BUILDING LESS SAFE. |
| | |
| | 2) M1.002: IT APPEARS A FIRE DAMPER IS MISSING WHERE |
| | THE O/A DUCT IS PENETRATION THE FIRE-RATED |
| | LOBBY/STAIRWAY EXTENSION WALL- SECTION 607.5.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |