| Plan Review Notes For Permit 18030309 |
| Permit Number |
18030309 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-24 13:19:53 | 2ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #18030309 | | | 4/17/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.002: IT APPEARS THAT THE 32"X20" O/A DUCT | | | IS LOCATED IN THE INTERIOR EXIT STAIRWAY EXTENSION | | | WHICH IS PROHIBITED PER SECTION 1023.5 FBC-17 BUILDING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|