| 2018-03-26 09:56:05 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING: FBC ACC |
| | A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM) |
| | MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. |
| | B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE |
| | 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE |
| | CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM) |
| | MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON |
| | THE OTHER SIDE. |
| | C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND |
| | 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO |
| | THE TOP OF THE GRIPPING SURFACE, |
| | |
| | 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE |
| | AND TOE CLEARANCE. PER FBC ACC 306 |
| | |
| | 3. PLEASE SHOW THE CLEAR FLOOR SPACE WITH THE |
| | DIMENSIONS SHOWN, FOR THE TOILETS, LAVATORY'S AND WATER |
| | FOUNTAIN. PER FBC ACC 604.3.1 - 606.2 - 602.2 |
| | |
| | 4. THE TOILET PAPER DISPENSER SHALL BE MOUNTED ON THE |
| | SIDE WALL IN FRONT OF THE TOILET SHT. I1.401 + I1.402 |
| | SHOW IT ON THE REAR WALL IT SHALL COMPLY WITH FBC ACC |
| | 604.7 |
| | |
| | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.1 + 602.2 + |
| | 602.4 + 602.7 |
| | |
| | 7. PLEASE SHOW ON THE WATER ISOMETRIC THE AIR HAMMER |
| | ARRESTORS AND SHUT OFF VALVES COMPILING WITH FBC PL |
| | 604.9 + 606.1 (5) |
| | |
| | 8. THE ISOMETRIC DRAWINGS ARE TO CONGESTED TO VERIFY |
| | CODE COMPLIANCE PLEASE EXPAND THE WATER AND SANITARY |
| | ISOMETRIC . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |