Plan Review Notes
Plan Review Notes For Permit 18030261
Permit Number 18030261
Review Stop E
Sequence Number 1
Notes
Date Text
2018-03-08 12:05:14FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SIGN PAGE MISSING FROM PERMIT PLEASE SUPPLY A SHEET
 SHOWING THE REQUIRED SIGNAGE AT THIS PV SYSTEM.
  
  
 690.17 (E) INTERRUPTING RATING. THE BUILDING OR
 STRUCTURE DISCONNECTING MEANS SHALL HAVE AN
 INTERRUPTING RATING SUFFICIENT FOR THE MAXIMUM CIRCUIT
 VOLTAGE AND CURRENT THAT IS AVAILABLE AT THE LINE
 TERMINALS OF THE EQUIPMENT. WHERE ALL TERMINALS OF THE
 DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN
 POSITION, A WARNING SIGN SHALL BE MOUNTED ON OR
 ADJACENT TO THE DISCONNECTING MEANS.
 THE SIGN SHALL BE CLEARLY LEGIBLE AND HAVE THE
 FOLLOWING WORDS OR EQUIVALENT:
  
 WARNING
 ELECTRIC SHOCK HAZARD
 DO NOT TOUCH TERMINALS.
 TERMINALS ON BOTH THE LINE
 AND LOAD SIDES MAY BE ENERGIZED
 IN THE OPEN POSITION.
  
 THE WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH
 110.21(B).
  
  
 690.31(G)(3) MARKING AND LABELING REQUIRED. THE
 FOLLOWING WIRING METHODS AND ENCLOSURES THAT CONTAIN PV
 POWER SOURCE CONDUCTORS SHALL BE MARKED WITH THE
 WORDING WARNING: PHOTOVOLTAIC POWER SOURCE BY MEANS OF
 PERMANENTLY AFFIXED LABELS OR OTHER APPROVED PERMANENT
 MARKING:
  
 (1) EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
 METHODS
 (2) COVERS OR ENCLOSURES OF PULL BOXES AND JUNCTION
 BOXES
 (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE
 CONDUIT OPENINGS ARE UNUSED
  
  
  
  
 690.31(G)(4) MARKING AND LABELING METHODS AND
 LOCATIONS. THE LABELS OR MARKINGS SHALL BE VISIBLE
 AFTER INSTALLATION. THE LABELS SHALL BE REFLECTIVE, AND
 ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM
 HEIGHT OF 9.5 MM (3?8 IN.) IN WHITE ON A RED
 BACKGROUND. PV POWER CIRCUIT LABELS SHALL APPEAR ON
 EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARATED BY
 ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
 SPACING BETWEEN LABELS OR MARKINGS, OR BETWEEN A LABEL
 AND A MARKING, SHALL NOT BE MORE THAN 3 M (10 FT).
 LABELS REQUIRED BY THIS SECTION SHALL BE SUITABLE FOR
 THE ENVIRONMENT WHERE THEY ARE INSTALLED.
  
  
  
 690.35(F) MARKING. THE PV POWER SOURCE SHALL BE LABELED
 WITH THE FOLLOWING WARNING AT EACH JUNCTION BOX,
 COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED,
 UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE:
  
 WARNING
 ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS
 OF THIS PHOTOVOLTAIC SYSTEM ARE
 UNGROUNDED AND MAY BE ENERGIZED.
 THE WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH
 110.21(B).
  
  
 690.56(B) FACILITIES WITH UTILITY SERVICES AND PV
 SYSTEMS. BUILDINGS OR STRUCTURES WITH BOTH UTILITY
 SERVICE AND A PV SYSTEM SHALL HAVE A PERMANENT PLAQUE
 OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
 DISCONNECTING MEANS AND THE PV SYSTEM DISCONNECTING
 MEANS IF NOT LOCATED AT THE SAME LOCATION. THE WARNING
 SIGN(S) OR LABEL(S) SHALL COMPLY WITH 110.21(B).
  