Plan Review Notes
Plan Review Notes For Permit 18030247
Permit Number 18030247
Review Stop B
Sequence Number 2
Notes
Date Text
2018-06-01 17:29:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE PLAN SHEETS ARE MISSING FROM THE TWO
 SETS OF PLANS THAT WERE RESUBMITTED. IT APPEARS THAT
 THE PERSON THAT DID THE RESUB DID NOT REMOVE THE PLAN
 SHEETS THAT WERE NOT REVISED FROM THE OLD PLAN SETS AND
 INSERT THEM INTO THE NEW ONES. ONLY ONE SET OF THE OLD
 PLANS WAS WITH THE RESUBMITTAL. SUBMIT TWO COMPLETE
 SETS OF PLANS. FBC 107.2.1
  
 2) THE PLANS DO NOT HAVE THE TITLE BLOCK OF THE
 ENGINEER THAT IS SIGNING AND SEALING THEM AS REQUIRED
 BY FAC 61G15-23.001 AND FS471.
  
 3) SUBMIT PROOF THAT THE METL-SPAN CFR INSULATED ROOF
 PANELS THAT ARE SHOWN ON SHEET DS-02 ARE THE ONES THAT
 WERE INSTALLED ON THIS COMMERCIAL BUILDING. FBC 107.2.1
  
 4) THE WINDLOAD DATA ON SHEET S-03 LISTS THIS PROJECT
 AS A RISK CATEGORY II WITH A 170 MPH VULT WINDSPEED.
 THIS BUILDING IS A SCHOOL AND IS CLASSIFIED AS RISK
 CATEGORY III WITH A 180MPH WIND SPEED PER FBC 1609.3.
 PLEASE REVISE THE WINDLOAD DATA.