| Plan Review Notes For Permit 18030247 |
| Permit Number |
18030247 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-01 17:29:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SOME OF THE PLAN SHEETS ARE MISSING FROM THE TWO | | | SETS OF PLANS THAT WERE RESUBMITTED. IT APPEARS THAT | | | THE PERSON THAT DID THE RESUB DID NOT REMOVE THE PLAN | | | SHEETS THAT WERE NOT REVISED FROM THE OLD PLAN SETS AND | | | INSERT THEM INTO THE NEW ONES. ONLY ONE SET OF THE OLD | | | PLANS WAS WITH THE RESUBMITTAL. SUBMIT TWO COMPLETE | | | SETS OF PLANS. FBC 107.2.1 | | | | | | 2) THE PLANS DO NOT HAVE THE TITLE BLOCK OF THE | | | ENGINEER THAT IS SIGNING AND SEALING THEM AS REQUIRED | | | BY FAC 61G15-23.001 AND FS471. | | | | | | 3) SUBMIT PROOF THAT THE METL-SPAN CFR INSULATED ROOF | | | PANELS THAT ARE SHOWN ON SHEET DS-02 ARE THE ONES THAT | | | WERE INSTALLED ON THIS COMMERCIAL BUILDING. FBC 107.2.1 | | | | | | 4) THE WINDLOAD DATA ON SHEET S-03 LISTS THIS PROJECT | | | AS A RISK CATEGORY II WITH A 170 MPH VULT WINDSPEED. | | | THIS BUILDING IS A SCHOOL AND IS CLASSIFIED AS RISK | | | CATEGORY III WITH A 180MPH WIND SPEED PER FBC 1609.3. | | | PLEASE REVISE THE WINDLOAD DATA. |
|