Plan Review Notes
Plan Review Notes For Permit 18030202
Permit Number 18030202
Review Stop M
Sequence Number 2
Notes
Date Text
2018-05-07 08:18:59MECHANICAL PROVISO
 5/7/2018
  
 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW
 CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS
 IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A
 PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER.
2018-04-23 12:23:142ND REVIEW FBC-2010 MECHANICAL
 THE BRISTOL
 REVISION #18030202
 MASTER #15111020
 4/23/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW
 CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS
 IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A
 PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER.
  
 3) PLEASE EITHER UPDATE SHEET M2.55B (18-19 TIER 2) TO
 MATCH THE REVISIONS SHOWN ON M2.55C (19 TIER 2) , OR
 ELIMINATE M2.55B AND REVISE M2.55C TO INCLUDE THE 18TH
 FLOOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  