| Plan Review Notes For Permit 18030202 |
| Permit Number |
18030202 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-05-07 08:18:59 | MECHANICAL PROVISO | | | 5/7/2018 | | | | | | 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW | | | CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS | | | IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A | | | PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER. | | 2018-04-23 12:23:14 | 2ND REVIEW FBC-2010 MECHANICAL | | | THE BRISTOL | | | REVISION #18030202 | | | MASTER #15111020 | | | 4/23/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW | | | CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS | | | IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A | | | PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER. | | | | | | 3) PLEASE EITHER UPDATE SHEET M2.55B (18-19 TIER 2) TO | | | MATCH THE REVISIONS SHOWN ON M2.55C (19 TIER 2) , OR | | | ELIMINATE M2.55B AND REVISE M2.55C TO INCLUDE THE 18TH | | | FLOOR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|