| 2018-03-21 16:00:51 | 1ST REVIEW FBC-2010 MECHANICAL |
| | THE BRISTOL |
| | REVISION #18030202 |
| | MASTER #15111020 |
| | 3/21/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M2.05- M2.25: PLEASE CLARIFY THE PURPOSE OF |
| | THE NEW SMOKE DAMPERS SHOWN ON THE O/A DUCT DROPS IN |
| | THE NORTH AND SOUTH CORE CEILINGS. CLARIFY HOW THE |
| | DAMPERS ARE TO BE ACTUATED AND IF THEY ARE PART OF THE |
| | SMOKE CONTROL SYSTEM. UPDATE ALL CONTROL DETAILS IF |
| | APPLICABLE. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE DAMPERS AND PROVIDE INSTALLATION DETAILS ON THE |
| | PLAN. |
| | |
| | 2) M2.05- M2.25 PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | FOR THE FIRE/SMOKE DAMPERS SHOWN IN THE CORES WHERE THE |
| | FLAMEBAR DUCT CONNECTS WITH THE CONVENTIONAL DUCTWORK. |
| | THE SPECS MUST INDICATE THAT THE PROPOSED INSTALLATIONS |
| | ARE CONSISTENT WITH THE UL 555, UL 555S, AND/OR UL 555C |
| | TESTING STANDARDS- SECTION 607.3.1. |
| | |
| | 3) M2.26: IT APPEARS THAT THE 12X12 AIR INTAKE BY THE |
| | NEW EF-R2 IS MISLABELED AND SHOULD BE LABELED AS AN |
| | EXHAUST OUTLET. |
| | |
| | 4) M.55B: BESIDES THE RELOCATION OF ONE HP, THE PLAN IS |
| | ALSO INDICATING OTHER HP CHANGES THROUGHOUT THE SPACE. |
| | PLEASE PROVIDE A MORE DESCRIPTIVE NARRATIVE THAT |
| | ITEMIZES ALL THE CHANGES, AND UPDATED ENERGY AND AC |
| | CALCULATIONS IF APPLICABLE. |
| | |
| | 5) M.55C: TO HELP EXPEDITE THE REVIEW, PLEASE UPLOAD |
| | THE ORIGINAL PLAN SHEET FOR COMPARISON. |
| | |
| | 6) M2.57B & M2.58B: THE DETAIL OF THE REROUTED DUCTS IN |
| | THE UTILITY ROOM IS INCOMPLETE- THE RETURN GRILLS AND |
| | FSD'S ARE NOT SHOWN. |
| | |
| | 7) M61.A: NO DUCTS ARE SHOWN ON THE PLAN- PLEASE |
| | CLARIFY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |