| Plan Review Notes For Permit 18030198 |
| Permit Number |
18030198 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-03-15 11:15:41 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | REVISION #18030198 | | | MASTER #15100707 | | | 3/15/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) BECASUE THE NEW ROOFTOP CONDENSER IS LESS THAN 10' | | | FROM THE EDGE OF THE ROOF, A MINIMUM 42" HIGH GUARD | | | SHALL BE IMSTALLED- SEE SECTION 304.11. THE GUARD SHALL | | | EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF THE | | | CONDENSER. | | | | | | 2) THE OWNER OF THE BUILDING OR ARCHITECT OF RECORD | | | MUST PROVIDE HIS/HER SIGNATURE ON THE LINE DESIGNATED | | | OWNER/AGENT ON THE CERTIFICATIONS PAGE 3 OF THE FLORIDA | | | ENERGYGAUGE COMPLIANCE REPORT- SECTION C103.1.1.2 | | | FBC-14 ENERGY CONSERVATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|