Plan Review Notes
Plan Review Notes For Permit 18030198
Permit Number 18030198
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-15 11:15:411ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 REVISION #18030198
 MASTER #15100707
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BECASUE THE NEW ROOFTOP CONDENSER IS LESS THAN 10'
 FROM THE EDGE OF THE ROOF, A MINIMUM 42" HIGH GUARD
 SHALL BE IMSTALLED- SEE SECTION 304.11. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF THE
 CONDENSER.
  
 2) THE OWNER OF THE BUILDING OR ARCHITECT OF RECORD
 MUST PROVIDE HIS/HER SIGNATURE ON THE LINE DESIGNATED
 OWNER/AGENT ON THE CERTIFICATIONS PAGE 3 OF THE FLORIDA
 ENERGYGAUGE COMPLIANCE REPORT- SECTION C103.1.1.2
 FBC-14 ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  