Plan Review Notes
Plan Review Notes For Permit 18030198
Permit Number 18030198
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-08 15:04:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18030198
 W. P. B. PERMIT: 15100707
 ADD: 831 BELVEDERE RD.
 CONT: AJS BUILDING
 TEL: 561-410-5162
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 08/2017
 ACTION: DENIED.
 1) THE ARCHITECTURAL SHEET A1 THE COVERSHEET LIST THE
 BUILDING TYPE AS II-B NON-COMBUSTIBLE. SHEET A2 INTHE
 FIRE PROOFING DETAILS LIST WOOD STUDS. SHEET A4 SHOWS
 ALL OF THE NEW WOOD TRUSSES AS WOOD, PLYWOOD SHEATHING.
 THE ENGINEERING PLANS 1 OF 5 SHOWS A NEW WOOD ROOFDECK,
 SHEET 2OF 5 SHOWS WOOD ROOF 2 X 12S ROOF JOIST, AND NEW
 2 PLY LVL BEAMS,
 WOOD MANSARD, SHEET 3 OF 5 PROVIDES WOOD FRAMING
 DETAILS OF WOOD ROOF JOIST AND WOOD INFILL OF EXTERIOR
 WALLS SHEET 4 OF 5 INDICATES NEW 2X10 ROOF JOIST AND
 WOOD FRAMED PARAPET WALLSAND SHEET 5OF 5 CUT SECTION OF
 WOOD MANSARD AND WOOD ROOFTRUSSES AND WOOD SCABS.
 THE 2017 FBC-B SECTION 603.1.1 ALLOWS FIRE RETARDANT
 TRATED WOOD IN:
 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2.NONBEARING EXTERIOR WALLS WHERE
 FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED.
 1.3.ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 2) PLEASE PROVIDE COMPLIANCE WITH: THE ENGINEERING
 SHEET 3 OF 5 INDICATES THE CLOSING UP OF A WINDOW WITH
 2X8 AND 5/8 INCH CDX PLYWOOD SHEATHING. THE PLANS
 INDICATE THE USE OF PAPERBACKED LATH BUT NOT THE 2ND OF
 2 LAYERS OF WATER-RESISTIVE BARRIER COMPLYING WITH ASTM
 E2556, TYPE I. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
 2017 FBC-B SECTION 2510.6 WATER-RESISTIVE BARRIERS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  