| Plan Review Notes For Permit 18030167 |
| Permit Number |
18030167 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-24 16:51:01 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18030167 | | | 4/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PLAN SHOWS RETURN AIR BEING TAKEN FROM THE | | | ADJACENT MAINTENANCE ROOM, HOWEVER THE CONTENTS OF THAT | | | ROOM ARE UNKNOWN, AND RETURN AIR FROM THAT ROOM MAY BE | | | PROHIBITED- SEE SECTION 601.5 ITEMS #1, 2 & 7. AND | | | VERIFY COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|