| Date |
Text |
| 2018-03-22 14:49:27 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL NOTE 1 AND 17 ON SHEETS CS-1 AND MEP 1 |
| | THROUGH 4 STATE THAT THE 2011 NEC IS USED FOR DESIGN. |
| | THIS IS NOT THE CURRENT CODE IN EFFECT. PROVIDE |
| | CORRECTIONS. FBC PREFACE |
| | 2. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN |
| | KITCHEN. NEC 210.8(B)(2) |
| | 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. WPB FBC 105.1, 107.2.1 |
| | 4. PANELS ARE SHOWN AS 3?, 120/240 VOLT, WHICH WOULD |
| | HAVE B? AS A HIGH LEG. HOWEVER, THE PANEL SCHEDULES |
| | SHOWS 120 VOLT LOADS ON B?. PROVIDE CLARIFICATION |
| | AND/OR CORRECTION. FBC 107.2.1 |
| | 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1, |
| | BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED |
| | TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE |
| | CORRECTION. FBC 107.2.1 |
| | 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC C405.6.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |