Notes
Date Text
2018-11-07 12:07:311ST REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC
 PERMIT #18030158
 3/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED REVISED AC PLAN BY THE CONTRACTOR
 NEEDS TO BEAR THE CONTRACTOR'S SIGNATURE AND LICENSE
 NUMBER.
  
 2) REQUIRED RETURN AIR FROM THE BEDROOMS, AND MAIN AC
 CLOSET RETURN GRILL NOT SHOWN- PLEASE CORRECT AND
 INCLUDE GRILL DIMENSIONS
  
 3) PLEASE NOTE THAT THE PROPOSED MECHANICAL PLAN IS
 DETERMINED TO BE A "REVISION" TO THE MAIN PERMIT PLANS
 ISSUED UNDER #17020233. PLEASE SUBMIT A REVISION
 APPLICATION FORM USING THE #18030158 AS THE REVISION
 NUMBER TO THE MASTER #17020233. A NEW SUB-PERMIT
 APPLICATION WILL ALSO HAVE TO BE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  