| 2019-04-25 10:49:30 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18030157 |
| | 4/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.0: COMMENT #7 FROM THE 2ND REVIEW STILL |
| | EXISTS- PLEASE COMPLY.7) M-1.0: DUCT SMOKE DETECTORS |
| | ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 5-TON AHU'S |
| | PER SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN |
| | EXEMPTION CAN BE APPLIED FOR THE 5-TON SYSTEMS IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE THOSE SYSTEMS |
| | ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| | AIR. |
| | |
| | 2) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE |
| | SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE |
| | MANUFACTURER'S SPECIFICATIONS, HOWEVWER THE COMCHECK |
| | ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS- |
| | PLEASE CORRECT. PLEASE NOTE THAT THE AC SCHEDULE |
| | INDICATES THE AIR HANDLERS ARE NOT EQUIPPED WITH HEAT |
| | STRIPS, HOWEVER MINIMUM HEAT IS REQUIRED FOR ALL |
| | OCCUPIED SPACES- SECTION 309.1 FBC M. |
| | |
| | 3) COMMENT #3 FROM THE 2ND REVIEW STILL PARTIALLY |
| | EXISTS. THE ELITE HVAC CALCS HAVE NOT BEEN PROVIDED |
| | WITH AN ORIGINAL SEAL AND SIGNATURE BY THE EOR. 3) |
| | ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE HVAC |
| | CALCS IS A COPIED, REDUCED IN SIZE INK SEAL. PROVIDE |
| | ORIGINAL 1-7/8" DIAMETER SEALS AND WET SIGNATURES ON |
| | THE DOCUMENTS- SECTION 61G15-23.002 (2) FAC. |
| | |
| | 4) PLEASE NOTE THAT THE AC CALCULATIONS ARE INDICATING |
| | ONLY TWO AIR HANDLERS- 1 & 2, HOWEVER THERE ARE 5 AIR |
| | HANDLERS IN THE SPACE. |
| | |
| | 5) COMMENT #8 FROM THE 2ND REVIEW STILL EXISTS- PLEASE |
| | COMPLY. 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE |
| | PLAN FOR THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT |
| | PROTECTION AND WIND LOAD ENGINEERING FOR INSTALLATION- |
| | SECTION 301.15 FBC M. |
| | |
| | 6) M-2.0: THE DETAIL PROVIDED FOR THE O/A ROOF FAN |
| | INSTALLATIONS USING A 6" DUCT EXTENSION ABOVE THE ROOF |
| | DOES NOT APPEAR TO BE APPLICABLE FOR THE SPECIFIED |
| | GREENHECK SAF FANS. THESE TYES OF ROOF FANS ARE |
| | TYPICALLY MOUNTED ON PRE-MANUFACTURED CURBS PER THE |
| | MANUFACTURER'S SPECIFICATIONS AND PER THE PRODUCT |
| | APPROVALS OR NOA'S. PLEASE SUBMIT THE SPECS AND THE |
| | NOA'S. |
| | |
| | 7) M-2.0: THE NEW AIR BALANCE SCHEDULE INDICATES |
| | GREATER AMOUNTS OF RETURN AIR TO THE SYSTEMS THAN THE |
| | AMOUNTS OF SUPPLY AIR PROVIDED? PLEASE SEE SECTION |
| | 601.5 (3) FBC M AND CORRECT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |