| 2019-04-29 15:34:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH |
| | CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5; |
| | WPB FBC 107.2.1 (THE PERMIT APPLICATION STATES THE WORK |
| | FOR THIS PLAN IS FOR 925 RAILROAD. THE ELECTRICAL PLAN |
| | SHOULD ONLY INCLUDE INFORMATION FOR WORK AT THAT |
| | ADDRESS. WHY ARE 2 SEPARATE RISER DIAGRAMS INCLUDED? |
| | PROVIDE CLARIFICATION AND/OR REMOVE INFORMATION NOT |
| | PERTINENT TO THIS PERMIT APPLICAITON.SOME SHEETS STATE |
| | THE WORK IS FOR 925 ADDRESS, SOME SHEETS STATE THE WORK |
| | IS FOR 925/1013, BUT THE FLOOR PLANS DO NOT INDICATE |
| | WHICH ADDRESS OR WHERE EXACTLY THE WORK IS TO BE |
| | PERFORMED.) |
| | 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE |
| | WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE |
| | CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY. |
| | NEC 220; WPB FBC 107.2.1(NOT CORRECTED. LOAD |
| | CALCULATION ON SHEET E2.0 STATES THE LOAD IS 440.59 |
| | AMPS, WHILE THE PANEL SCHEDULE FOR THE SAME SERVICE |
| | STATES THE LOAD AS 251 AMPS. PROVIDE CORRECTION AS |
| | PREVIOUSLY REQUESTED.) |
| | 3. CORRECTED. |
| | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT |
| | INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF |
| | LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE. |
| | SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2 (NOT |
| | PROVIDED.) |
| | 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS |
| | PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW |
| | IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE |
| | NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1(COMMENT |
| | STILL APPLIES.) |
| | |
| | NEW COMMENT: |
| | |
| | 6. FOR NEW SERVICE ON SHEET E2.0, PROVIDE AVAILABLE |
| | SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING |
| | INFORMATION FROM THE POWER COMPANY STATING WHAT THE |
| | AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO |
| | CONFIRM THE AIC RATING OF THE SERVICE EQUIPMENT IS |
| | ADEQUATE. PROVIDE AIC RATING OF ELECTRICAL PANELS.NEC |
| | 110.9, 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |