| 2018-08-28 12:05:05 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SCOPE OF WORK HAS CHANGED DUE TO THE CHANGE OF |
| | OCCUPANCY. ADDITIONAL REVIEWS REQUIRED - MECH., |
| | ELECTRICAL, PLUMBING AND ZONING. |
| | FBC EXISTING SEC. 1001.2.2 CHANGE OF OCCUPANCY |
| | CLASSIFICATION OR GROUP. |
| | WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| | CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| | SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| | CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN |
| | OCCUPANCY CLASSIFICATION. |
| | |
| | 2. CHANGE CLASSIFICATION OF WORK ON PLAN PAGE CV-1.0 |
| | FROM ALTERATION LEVEL II TO CHANGE OF OCCUPANCY. NEW |
| | CLASSIFICATION SHOULD BE A-3 GALLERY. |
| | 303.4 ASSEMBLY GROUP A-3. |
| | GROUP A-3 OCCUPANCY INCLUDES ASSEMBLY USES INTENDED FOR |
| | WORSHIP, RECREATION OR AMUSEMENT AND OTHER ASSEMBLY |
| | USES NOT CLASSIFIED ELSEWHERE IN GROUP A INCLUDING, BUT |
| | NOT LIMITED TO: |
| | ART GALLERIES |
| | |
| | 3. APPLICABLE BUILDING CODES ON PLAN PAGE C-1 ARE |
| | INCORRECT. CURRENT GOVERNING CODE IS THE 2017 FBC |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 4. DRAWING SCHEDULE ON PLAN PAGE C-1 IS INCORRECT. |
| | COVER SHEET IS CV-1.0. SITE PLAN IS C-1. |
| | |
| | 5. DRAWING SCALE ON PLAN PAGES A-1, A-2 AND A-3 IS TOO |
| | SMALL. MINIMUM SCALE IS 1/8" = 1 FOOT. |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 6. MINIMUM NUMBER OF PLUMBING FACILITIES SHALL COMPLY |
| | WITH FBC CHPT. 29. |
| | FBC 2902.1 MINIMUM NUMBER OF FIXTURES. |
| | PLUMBING FIXTURES SHALL BE PROVIDED IN THE MINIMUM |
| | NUMBER AS SHOWN IN TABLE 2902.1 BASED ON THE ACTUAL USE |
| | OF THE BUILDING OR SPACE. USES NOT SHOWN IN TABLE |
| | 2902.1 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE |
| | OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE DETERMINED |
| | BY THIS CODE. |
| | |
| | 7. REFERENCE PLAN PAGE S-1.0 FOR THE FOLLOWING |
| | COMMENTS. |
| | 7A. PROVIDE DESIGN WIND LOADS FOR CONTAINERS. |
| | ENGINEERING TO BE SIGNED AND SEALED BY A DESIGN |
| | PROFESSIONAL. |
| | 7B. PROVIDE DESIGN FOR FOUNDATION. IF EXISTING, PROVIDE |
| | CERTIFICATION BY A DESIGN PROFESSIONAL. |
| | 7C. PROVIDE ATTACHMENT DETAIL FOR CONTAINER TO |
| | FOUNDATION. |
| | 7D. PROVIDE WELD SPECIFICATIONS. |
| | 7E. PROVIDE WELDER CERTIFICATIONS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |