| 2018-03-08 05:31:27 | 03/08/2018 PLUMBING 1ST REVISION REVIEW**DENIED** |
| | |
| | 1) THIS IS A CHANGE OF OCCUPANCY AS THE EXISTING |
| | GOODWILL PERMIT #03040660 WAS LISTED AS A GROUP F- |
| | FACTORY INDUSTRIAL. PER FBC-EXISTING 1001.3 THE |
| | PROVISIONS OF SECTIONS 1002 THROUGH 1012 SHALL APPLY. |
| | FOR PLUMBING THIS WILL AFFECT THE ACCESSIBILITY OF THE |
| | RESTROOMS THAT ARE NOT CURRENTLY IN COMPLIANCE WITH THE |
| | FBC-ACCESSIBILITY . LIST ON PLAN THAT THIS IS A CHANGE |
| | OF OCCUPANCY. |
| | |
| | 2) SHOW THE REAR GRAB BAR AS BEING MOUNTED 12" OFF |
| | CENTER LINE OF THE TOILET AS YOU CURRENTLY SHOW 4? THIS |
| | WOULD BE INCORRECT IF THE TOILET IS INSTALLED @ 18? AS |
| | SHOWN AS THE MAX ON YOUR PLAN IT WOULD MAKE THE GRAB |
| | BAR 6? OFF THE SIDE TO BE COMPLAINT. FBC-A 604.5.2 |
| | |
| | 3) SHOW ALL REQUIRED CLEAR FLOOR SPACES FOR THE TOILET |
| | COMPARTMENTS. FBC-A 604.9 |
| | |
| | 4) SHOW CLEAR FLOOR SPACE FOR EACH OF THE REQUIRE |
| | NUMBER OF COMMON USE SINKS IN THE RESTROOMS WITH KNEE |
| | AND TOE CLEARANCE. FBC-A 606.2 |
| | |
| | 5) SHOW SINKS HEIGHT MAX AS BEING 34" FBC-A 606.3 |
| | |
| | 6) SHOW REQUIRED NUMBER OF FIXTURES FOR OCCUPANT LOAD |
| | NEEDED. FBC-P 403.1 |
| | |
| | 7) SHOW DIMENSIONS OF ALL WALLS ( LENGTH AND WIDTH ) OF |
| | ALL RESTROOMS INCLUDING STALLS. FBC 107.2.1 |
| | |
| | 8) ALL FIXTURES BEING RE-USED MUST MEET ALL |
| | REQUIREMENTS SET FORTH IN THE FBC-P 2014 AND NSF61 |
| | |
| | 9) VALUE OF JOB SHALL BE CORRECT TO ADJUST FOR REQUIRED |
| | CHANGES. WPB AMEND TO THE FBC 109.3 BUILDING VALUATION |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |